- RP relief valve: minimum opening point
- 2.0 psid or higher
- RP check valve one: minimum differential
- 5.0 psid or higher
- RP buffer requirement
- Check valve one at least 3.0 psid above the relief valve opening point
- Double check: minimum differential per check
- 1.0 psid or higher, and drip tight
- PVB and SVB air inlet: minimum opening point
- 1.0 psi or higher above atmosphere, and it must open fully
- PVB and SVB check valve: minimum differential
- 1.0 psid or higher
- RP check valve two: what is it tested for
- Tightness against backpressure, and 1.0 psid on the final differential reading
Dimensions
- PVB height above the highest downstream outlet
- At least twelve inches
- AVB height above the outlets
- At least six inches
- Air gap, clear of obstructions
- Twice the effective opening, never less than one inch
- Air gap, affected by a near wall
- Three times the effective opening
- Assembly height above grade
- About twelve inches minimum to the bottom, about thirty inches maximum to the centre line
- Barometric loop height
- About thirty five feet, since the atmosphere supports about thirty four feet of water
Hydraulics
- Feet of water supported by one psi
- 2.31 feet
- Pressure produced by one foot of water
- 0.433 psi
- Feet of water per inch of mercury
- 1.133 feet
- Atmospheric pressure at sea level
- 14.7 psi, about 29.9 inches of mercury, about 34 feet of water
- Gallons per minute to cubic feet per second
- Divide by 448.83
- A gauge held below the reference point reads
- High, by 0.433 psi for every foot
Standards
- ASSE 1013
- Reduced pressure principle assembly
- ASSE 1015
- Double check valve assembly
- ASSE 1020
- Pressure vacuum breaker assembly
- ASSE 1056
- Spill-resistant vacuum breaker assembly
- ASSE 5110
- Backflow prevention assembly tester certification
- ASSE 5120, 5130 and 5150
- Cross-connection control surveyor, repairer and programme administrator
- AWWA C510
- Double check valve assembly product standard. C511 is the reduced pressure principle assembly
Selection
- High hazard with backpressure
- Reduced pressure principle assembly, and nothing less
- High hazard, backsiphonage only
- PVB, SVB or RP. Never a double check
- Low hazard with backpressure
- Double check as the minimum, RP always acceptable
- What a vacuum breaker cannot do
- Resist backpressure, at any hazard level and any height
- Classification of lawn irrigation
- A health hazard, because of what is in the soil
- The only protection against every degree of hazard
- An air gap
Procedure
- Test cock flushing order
- Open four, three, two, one. Close one, two, three, four
- PVB test order
- Air inlet first, then the check valve
- SVB test order
- Check valve first, then the air inlet
- Test cocks straddling RP check valve one
- Test cocks two and three
- Test cocks straddling check valve two
- Test cocks three and four
- How far to open the low control for a relief valve reading
- No more than a quarter turn, so the pressure falls slowly
- Why reset the gauge before reading check valve one
- To relieve disc compression, which otherwise reads high
- Two drips from an RP relief vent after a reset
- Check valve two has failed under backpressure
- Identifying an assembly by its test cocks
- Four means RP or DC, two means PVB, one plus a vent means SVB
Administration
- How often an installed assembly is tested
- Annually in most jurisdictions
- How often a tester certificate is renewed
- Every three years in most programmes. Washington is annual
- Gauge calibration interval
- Within the twelve months before the test
- Texas continuing education requirement
- Twenty four hours over a three year licence term
- California accreditation deadline
- 1 July 2027, when only ANSI accredited bodies count
- Ohio certificate classes
- A for general isolation, B for irrigation, C for purveyor owned
- Who receives a completed test report
- The water purveyor and the property owner
Troubleshooting
- The fault that imitates every other fault
- A leaking number one shut-off valve
- Relief valve discharging only under downstream demand
- A hydraulic problem with the supply, not a component failure
- Intermittent relief discharge after new plumbing work
- Thermal expansion in a newly closed system
- A needle that bounces and will not settle
- Air in the hoses, or flow still moving through the assembly