18 things backflow testers hear on the job, each checked against the field test criteria, the product standards and the state rules, with the source that settles it.

Myth 1 of 18

What you hear

A backflow tester certificate has to be renewed every year.

All 18 myths

  1. A backflow tester certificate has to be renewed every year.

    In almost every programme it runs three years. ASSE, Texas, Ohio and California are all three year cycles. What is annual is the test of each installed device, and the two get confused constantly. Washington is the genuine exception, renewing the tester annually.

    ASSE recertification policy; TCEQ; OAC 1301:3-7-02; WAC 246-292

  2. A high hazard always needs a reduced pressure assembly.

    Only if backpressure is possible. A lawn irrigation system with no pump and no injector is a health hazard, and a pressure vacuum breaker is acceptable on it. The moment an injector or a pump appears the answer changes to an RP.

    Standard selection practice, AWWA M14

  3. If check valve one reads above five, the RP passes.

    Check valve one also has to sit at least 3.0 psid above the relief valve opening point. An assembly reading 5.5 with a relief valve opening at 3.5 has two individually passing numbers and a buffer of only 2.0, and it fails.

    USC field test criteria

  4. Irrigation is a low hazard because it is only water going in.

    It is a health hazard, and the reason is what is in the soil rather than what goes into the pipe. Fertiliser, pesticide and animal waste are all sitting where a siphon would draw from.

    Standard hazard classification

  5. A vacuum breaker fitted high enough will handle backpressure.

    Height has nothing to do with it. A vacuum breaker protects against backsiphonage only, and backpressure pushes straight past it whatever the installation height or the hazard level.

    ASSE 1020 and ASSE 1056

  6. The gauge can be held wherever is convenient.

    The centre line has to be level with the test cock reference point. Every foot off level shifts the reading by 0.433 psi, and against a 1.0 psid criterion on a double check, two feet of error is most of the available margin.

    AWWA M14 Appendix B

  7. A failed test still counts as this year's annual test.

    It does not. The assembly is still the unprotected one it was before you arrived. The clock runs from the passing retest, and treating a failure as a completed annual is how an assembly sits broken for a year.

    Standard purveyor practice

  8. A relief valve that drips means the assembly needs rebuilding.

    Not necessarily. If the discharge stops when a downstream valve closes, the supply cannot hold the margin at that flow, and that is a hydraulic problem. An intermittent drip after new plumbing work is usually thermal expansion in a newly closed system.

    Standard troubleshooting practice

  9. An air inlet that will not open means a failed air inlet.

    A leaking number one shut-off keeps feeding the body so the pressure never falls far enough for the inlet to act. Work the shut-off open and closed and try again before condemning anything. Getting this wrong means replacing the wrong part.

    Manufacturer field procedures for ASSE 1020

  10. The relief port can be piped straight into a floor drain.

    It discharges to atmosphere through an air gap. A direct connection makes the drain itself the cross-connection the assembly was fitted to eliminate, and it can siphon the drain contents into the reduced pressure zone.

    Standard installation requirement

  11. A double check is fine anywhere as long as it passes its test.

    It is not approved for a health hazard, whatever it reads. Two checks in series are two silent barriers, and nothing on the assembly tells anybody when the first one has stopped sealing.

    ASSE 1015 application limits

  12. A passing test means the connection is properly protected.

    Only if the right assembly is fitted for the hazard, and fitted correctly. A perfect set of readings on a double check protecting a boiler feed still leaves the water unprotected, and the tester's name is on the report.

    Standard tester responsibility

  13. An atmospheric vacuum breaker can be left under pressure if it is installed high enough.

    It cannot. The usual limit is twelve hours in any twenty four, and it must sit downstream of the last control valve. Continuous pressure holds the poppet on its seat until it sticks there, and a stuck poppet gives no warning at all.

    ASSE 1001 application limits

  14. Calibrating your own gauge against a second one is good enough.

    In the stricter jurisdictions it is not. Washington requires the kit to be evaluated for performance, pressure tested and checked for accuracy by an independent laboratory within the twelve months before the test. A shop check by the gauge owner does not satisfy it.

    WAC 246-292-034

  15. An air gap only has to be one inch.

    One inch is a floor, not the rule. The gap is twice the effective opening, or three times where a near wall affects it, and the one inch minimum only governs when the multiplier gives less than that.

    ASME A112.1.2, adopted by the plumbing codes

  16. The PVB and the SVB are tested the same way.

    The criteria are identical and the order is reversed. A PVB tests the air inlet first. An SVB tests the check valve first, because its vent valve brings the body to atmosphere without spilling.

    ASSE 1020 and ASSE 1056 field procedures

  17. An elevated tank with no pump cannot cause backpressure.

    Elevation is a pressure source. A tank on a roof pushes down its own fill line with no pump anywhere on the property, and it has to be treated as a backpressure condition.

    Standard hazard evaluation practice

  18. A gauge reading of zero means the check valve has failed.

    It has four common causes and three of them are the tester. Hoses on the wrong test cocks, a needle valve left open and air that was never purged all produce the same result. Check the kit before condemning the assembly.

    Standard field practice