EPA Section 608 Certification
Flashcards
70 cards on Section 608. Turn each one over, then say whether you knew it. The ones you didn't come round again.
Card 1 of 700 knew it · 0 again
Swipe right if you knew it, left to see it again. On a keyboard: Enter turns the card, the arrow keys mark it.
All 70 cards
Dates
- When did venting CFCs and HCFCs become illegal?
- 1 July 1992
- When was the venting ban extended to substitutes such as HFCs?
- 15 November 1995
- When did US CFC production end?
- 1 January 1996
- When did R-22 production and import end?
- 1 January 2020
- What changed on 1 January 2025?
- R-410A restricted in new residential and light commercial equipment, under the AIM Act Technology Transitions Rule
- What is the significance of 15 November 1993?
- The cut-off date that splits the recovery equipment and evacuation requirement tables
Definitions
- Recovery
- Removing refrigerant from an appliance and storing it externally. No cleaning implied.
- Recycling
- Cleaning refrigerant for reuse by oil separation and filter driers. Same owner only.
- Reclaim
- Reprocessing to AHRI 700 purity, verified by laboratory analysis. Required before sale to a new owner.
- Small appliance
- Fully manufactured, charged and hermetically sealed in a factory with 5 lb of refrigerant or less
- De minimis release
- A small release that happens despite a good faith attempt to recover. Not a size allowance.
- Temperature glide
- The difference between the bubble point and the dew point at the same pressure
- Fractionation
- A blend's components separating, so the composition of what remains is no longer correct
Thresholds
- Comfort cooling leak rate trigger
- 10% per year
- Commercial refrigeration leak rate trigger
- 20% per year
- Industrial process refrigeration leak rate trigger
- 30% per year
- Charge size at which leak rules apply
- 50 pounds or more for ozone-depleting refrigerants (Section 608). Since 1 January 2026, 15 pounds or more for HFCs with a GWP above 53 (AIM Act, 40 CFR 84.106).
- Deadline to repair a leak once triggered
- 30 days from discovery
- How long must Section 608 records be kept?
- Three years
- Maximum fill for a recovery cylinder
- 80 percent by weight
- Cylinder hydrostatic retest interval
- Five years
- Maximum safe cylinder temperature
- 125 degrees F
- Passing score on each 608 section
- 70 percent, so 18 of 25 questions
Evacuation
- Low pressure appliance evacuation requirement
- 25 mm Hg absolute
- High pressure appliance under 200 lb
- 0 in Hg, meaning atmospheric pressure
- High pressure appliance 200 lb or more, made after 15 Nov 1993
- 10 in Hg vacuum
- Medium pressure appliance 200 lb or more, made after 15 Nov 1993
- 15 in Hg vacuum
- Very high pressure appliance
- 0 in Hg, whatever the date
- Small appliance, compressor working, modern equipment
- 90 percent recovery
- Small appliance, compressor not working
- 80 percent recovery
- Small appliance alternative to the percentage
- Evacuate to 4 in Hg vacuum
Certification
- Type I covers
- Small appliances, holding 5 lb or less and sealed at the factory
- Type II covers
- High, very high and medium pressure appliances
- Type III covers
- Low pressure appliances, such as R-11 and R-123 chillers
- How do you get Universal certification?
- Pass Core plus all three type sections. There is no separate Universal exam.
- When does Section 608 certification expire?
- Never
A2L
- What does A2L mean?
- Lower toxicity, mildly flammable, burning velocity 10 cm/s or less
- What is R-454B made of?
- About 68.9% R-32 and 31.1% R-1234yf by mass
- How are A2L cylinders identified?
- Red band or flame marking, and a left-hand threaded valve outlet
- Does Section 608 certification cover A2L work?
- Yes. Employer and manufacturer A2L training is separate and often required.
- Can A1-rated recovery equipment be used on A2L?
- No. The equipment must be listed for flammable refrigerant.
Diagnosis
- Superheat is measured from which saturation point?
- The dew point
- Subcooling is measured from which saturation point?
- The bubble point
- High superheat and low subcooling
- Undercharge
- High superheat and high subcooling
- Restriction between the condenser and the coil
- Low superheat and high subcooling
- Overcharge
- How is a TXV system charged?
- By subcooling. The valve holds its own superheat.
- How is a fixed orifice system charged?
- By superheat, against a target from indoor wet bulb and outdoor dry bulb
- Target superheat formula
- (3 x indoor wet bulb - 80 - outdoor dry bulb) / 2
- Compression ratio
- Absolute discharge divided by absolute suction. Add 14.7 to both gauge readings first.
Formulas
- Sensible heat equation
- Btu/h = 1.08 x cfm x temperature difference, at sea level
- Capacitance from volts and amps
- uF = 2652 x amps / volts, at 60 Hz
- Total external static pressure
- The size of the supply reading plus the size of the return reading
- Friction rate for duct design
- Available static x 100, divided by total effective length
- The three fan laws
- Airflow follows speed, pressure follows the square, power follows the cube
- One ton of refrigeration
- 12,000 Btu/h
- Design airflow per ton
- 350 to 450 cfm per ton
- Minimum circuit ampacity
- 1.25 x largest motor, plus all other loads at 100 percent
- Which way is MOCP rounded?
- Down to the next standard breaker size, never up
Oils
- Which oil goes with HFC refrigerants?
- POE, and it absorbs moisture from the air within minutes
- Which oil goes with CFC and HCFC refrigerants?
- Mineral oil or alkylbenzene
- What happens if mineral oil is used with an HFC?
- The oil logs in the evaporator and never returns to the compressor
Safety
- What gas is used to pressure test a system?
- Dry nitrogen, with a regulator and relief valve. Never oxygen or compressed air.
- Why never oxygen?
- Oxygen and refrigerant oil under pressure can explode
- Recovery cylinder colour
- Grey body with a yellow shoulder
- What is the main hazard of a large leak indoors?
- Oxygen displacement and asphyxiation. Refrigerant is heavier than air and pools low.
- Refrigerant on hot metal or a flame produces
- Toxic decomposition products, including hydrogen fluoride and phosgene
- Rupture disc setting on a low pressure chiller
- About 15 psig, so leak testing stays below 10 psig
- Why must chiller refrigerant stay above 32 F during recovery?
- Water in the tubes freezes and splits them
- Who can buy refrigerant for stationary equipment?
- A Section 608 certified technician, or someone employing one