30 things technicians hear on the job, each checked against the EPA rules, the standards and good service practice, with the source that settles it.
What you hear
A small release of refrigerant is fine as long as it is under a pound.
All 30 myths
A small release of refrigerant is fine as long as it is under a pound.
There is no size allowance. The only exception is a de minimis release that occurs despite a good faith attempt to recover, which is about procedure rather than quantity.
40 CFR 82.154
HFCs can be vented because they do not harm the ozone layer.
The venting prohibition was extended to substitutes on 15 November 1995 and does not depend on ozone depletion potential. R-410A and R-454B may not be vented.
40 CFR 82.154
Purging the hoses before disconnecting is normal practice.
It is a knowing release. Low loss fittings and recovering the hose contents are the correct practice.
40 CFR 82.154
A 20 degree delta-T means the system is working correctly.
The correct target moves with the entering air humidity. In humid conditions 14 degrees can be right, and in dry conditions 22 degrees can be right.
Target delta-T charts
A wide temperature split means the system is cooling well.
A wide split usually means too little air over the coil. The system is starved, not performing.
Airflow diagnosis
You charge a TXV system by superheat.
The valve holds superheat constant regardless of charge, so superheat says nothing about it. Subcooling is the number that responds.
Manufacturer charging procedures
Superheat is superheat, whatever refrigerant is in the system.
On a zeotropic blend it must be measured from the dew point. Using the bubble point instead inflates the answer by the whole glide, which is over 10 degrees on R-407C.
Blend charging practice
You can top up a leaking blend and it will be fine.
A leak changes the composition of what remains, so adding more never restores the original mixture. Repair, recover and weigh in a fresh charge.
Fractionation
Compression ratio is discharge pressure divided by suction pressure.
Both readings must be converted to absolute first by adding atmospheric pressure. A ratio of two numbers measured from an arbitrary zero has no meaning.
Refrigeration fundamentals
Section 608 certification has to be renewed every few years.
It never expires. Additional A2L or manufacturer training is a separate matter and may be required by an employer.
40 CFR 82.161
A2L refrigerants need a new federal certification.
Existing Section 608 certification remains valid. What changes is the equipment rating, the ignition control and the charge limits.
40 CFR 82.161
R-410A systems became illegal to service in 2025.
The restriction applies to manufacturing and importing new equipment. Existing R-410A systems will be serviced normally for the rest of their lives.
AIM Act Technology Transitions Rule
You can use your normal recovery machine on R-454B.
Recovery equipment, hoses and cylinders must be rated for flammable refrigerant. An unrated machine puts an ignition source inside a flammable atmosphere.
UL 60335-2-40
Bubbles in the sight glass always mean the system is low on charge.
On a zeotropic blend, flash can appear at correct charge. Subcooling is the measurement that settles it.
Blend charging practice
A vacuum pump can be used to recover refrigerant if you are careful.
A vacuum pump exhausts to the room, so using it to remove refrigerant is a direct venting violation. It also destroys the pump oil.
40 CFR 82.154
Twenty-nine inches on the compound gauge means the system is dry.
The whole useful evacuation range sits in the last inch of that gauge. Only a micron gauge resolves it, and only a decay test proves the system is dry.
Evacuation practice
A disposable cylinder can be refilled if you clean it first.
Refilling a disposable cylinder is a DOT violation and a documented cause of injury. They have no protective cap and are not built for refilling.
DOT cylinder requirements
Compressed air is fine for pressure testing if you have no nitrogen.
Compressed air carries moisture into the system and is an oxidiser. Oxygen with refrigerant oil under pressure can detonate.
Standard service practice
If the head pressure is high, the system must be overcharged.
Non-condensables, a dirty condenser and a restriction all raise head pressure too. Subcooling is what separates overcharge from the others.
Refrigeration diagnosis
Superheat measured at the condensing unit can be compared against an evaporator target.
A long suction line through a hot attic adds ten degrees or more. Judging that reading against a coil target condemns healthy systems.
Charging practice
A low pressure chiller leaks refrigerant out, like any other system.
It runs in a vacuum, so a low side leak draws air and moisture in. That is why purge units exist and why purge run time is the leak indicator.
Low pressure appliance practice
Any recovery machine will do for a chiller.
Low pressure appliances require equipment certified to reach 25 mm Hg absolute. A high pressure recovery machine cannot get there.
40 CFR 82.158
You only need to recover before scrapping an appliance, not before repairing it.
The prohibition is about opening the system, not about the reason for opening it.
40 CFR 82.154
Recovered refrigerant can be sold on to another customer.
Refrigerant sold to a different owner must first be reclaimed to AHRI 700 purity by a certified reclaimer. Same owner reuse is permitted.
40 CFR 82.154
Speeding the blower up a little will not affect the motor much.
Power follows the cube of speed. Twenty percent more speed is seventy-three percent more motor load.
Fan laws
Ducts can be sized from a chart without working out a friction rate.
The chart has a friction rate axis. Without knowing the available static and the total effective length, the size chosen is a guess.
Duct design method
The breaker should be rounded up to the next size if the calculation falls between.
Maximum overcurrent protection is rounded down. A breaker larger than the calculated maximum does not protect the equipment.
NEC 440.22 method
A capacitor tests fine if the motor runs.
A capacitor well outside tolerance still lets a motor run, hotter and less efficiently, until it fails and takes the motor with it. Measure it under load.
Electrical testing practice
A two percent voltage imbalance is trivial.
Two percent is not trivial: a small voltage imbalance produces a current imbalance six to ten times larger, and that current becomes heat in the windings. NEMA MG-1 calls for derating a motor above 1 percent, and many equipment makers allow no more than 2.
NEMA MG-1
Adding refrigerant to a system that is low is a complete repair.
A sealed system does not consume refrigerant. If it is low, it leaked, and the leak rules exist to stop repeated topping up.
40 CFR 82.157