48 HVAC symbols you'll see on a set of plans, each drawn the way it appears on the page, with its abbreviation and what it means.
48 symbols
Refrigeration Circuit
CompressorCOMP
A circle with a wedge or a filled segment. The heart of the circuit: it raises pressure, not temperature directly.
Refrigeration Circuit
CondenserCOND
A rectangle with internal serpentine lines, usually with a fan symbol beside it. Rejects heat and turns vapour to liquid.
Refrigeration Circuit
EvaporatorEVAP
Same serpentine rectangle as the condenser, on the low side of the circuit. Absorbs heat and boils liquid to vapour.
Refrigeration Circuit
Thermostatic Expansion ValveTXV
A valve body with an external sensing bulb line running to the suction line. Modulates to hold a set superheat.
Refrigeration Circuit
Fixed Orifice / PistonORIF
A simple restriction in the liquid line with no sensing line. Cannot adjust to conditions, so superheat varies with charge and weather.
Refrigeration Circuit
Capillary TubeCAP
A long coiled line drawn between condenser and evaporator. The metering device on most small sealed appliances.
Refrigeration Circuit
Filter DrierFD
A cylinder in the liquid line, often with an arrow showing flow direction. Removes moisture and traps debris.
Refrigeration Circuit
ReceiverRCVR
A horizontal vessel after the condenser. Stores liquid where the charge requirement varies with load.
Refrigeration Circuit
AccumulatorACC
A vertical vessel in the suction line with an internal J-tube. Traps liquid before it can reach the compressor.
Refrigeration Circuit
Reversing ValveRV
A four port valve with a solenoid. Swaps the roles of the indoor and outdoor coils on a heat pump.
Refrigeration Circuit
Sight GlassSG
A small circle in the liquid line, often with a moisture indicator. Bubbles mean flash gas, though not reliably on a blend.
Refrigeration Circuit
Service ValveSV
A valve with a gauge port. Front seated isolates the system, back seated isolates the port.
Refrigeration Circuit
Schrader ValveSCH
A spring loaded core in a service port. The cap is a genuine second seal, not decoration.
Refrigeration Circuit
Check ValveCV
An arrow or a ball in a seat, allowing flow one way only. Common in heat pump circuits around the metering devices.
Refrigeration Circuit
Solenoid ValveSOL
A valve body with a coil drawn on top. Electrically operated, used for pump down and liquid line control.
Refrigeration Circuit
Oil SeparatorOS
A vessel in the discharge line with a float and a return line to the crankcase. Used where oil return is difficult.
Air Side & Ductwork
Supply AirSA
An arrow pointing away from the unit, often labelled SA. Conditioned air leaving toward the space.
Air Side & Ductwork
Return AirRA
An arrow pointing toward the unit, labelled RA. Where static pressure reads negative on a manometer.
Air Side & Ductwork
Outside AirOA
An arrow entering from outside the building envelope, labelled OA. Ventilation air.
Air Side & Ductwork
Volume DamperVD
A line drawn diagonally across the duct with a handle. Balances flow between branches.
Air Side & Ductwork
Fire DamperFD
A damper symbol with FD marked. Closes on heat to stop fire spreading through the duct.
Air Side & Ductwork
Flexible ConnectionFLEX
A zigzag or hatched section between the unit and the duct. Stops blower vibration carrying into the ductwork.
Air Side & Ductwork
Duct TransitionTRANS
A tapered section changing size or shape. Abrupt transitions add far more effective length than gradual ones.
Air Side & Ductwork
Turning VanesTV
Curved lines drawn inside a square elbow. Cut the effective length of the elbow substantially.
Electrical & Controls
ContactorC
A coil symbol with a set of normally open contacts. Energising the coil closes the contacts and starts the compressor.
Electrical & Controls
Run CapacitorRC
Two parallel lines, one sometimes curved. Provides the phase shift a single phase motor needs to run efficiently.
Electrical & Controls
Start CapacitorSC
A capacitor symbol in series with a start relay. In circuit only during starting, then dropped out.
Electrical & Controls
Normally Open ContactNO
Two parallel vertical lines with a gap. Open at rest, closed when its coil is energised.
Electrical & Controls
Normally Closed ContactNC
Two parallel lines with a diagonal slash. Closed at rest, opened when its coil is energised.
Electrical & Controls
High Pressure SwitchHPS
A pressure sensing symbol, normally closed, opening on a rise. Protects against a blocked condenser or overcharge.
Electrical & Controls
Low Pressure SwitchLPS
A pressure sensing symbol, normally closed, opening on a fall. Protects against loss of charge.
Electrical & Controls
Overload ProtectorOL
A bimetal or thermal symbol in series with the motor. Opens on excessive current or winding temperature.
Electrical & Controls
TransformerXFMR
Two coils side by side. Steps line voltage down to the 24 volt control circuit.
Electrical & Controls
Crankcase HeaterCCH
A resistive element symbol at the compressor. Stops refrigerant condensing into the oil during off cycles.
Electrical & Controls
Defrost ControlDFB
A timer or board symbol on a heat pump. Reverses the cycle to clear ice from the outdoor coil.
Electrical & Controls
A2L Leak SensorA2L
A sensor symbol wired to the control board on A2L equipment. Triggers the blower and locks out ignition sources on a leak.
Gas Heat
Gas ValveGV
A valve body with one or two solenoid coils. Redundant coils are standard on modern furnaces.
Gas Heat
Inducer MotorIND
A small blower symbol upstream of the burners. Proves draught before the gas valve is allowed to open.
Gas Heat
Pressure SwitchPS
A diaphragm switch sensing inducer draught. If it does not make, the furnace will not fire.
Gas Heat
Flame SensorFS
A single rod in the flame. Uses flame rectification, so it senses current in microamps rather than heat.
Gas Heat
High Limit SwitchLIM
A temperature switch in the heat exchanger compartment. Trips on low airflow, which is what a high temperature rise causes.
Gas Heat
Rollout SwitchRO
A manual reset thermal switch at the burner. Trips when flame rolls out of the heat exchanger, which means a blocked flue or a crack.
Cylinder & Equipment Labels
A2L Flame MarkingA2L
A red flame symbol or red band near the cylinder shoulder. Marks a mildly flammable refrigerant.
Cylinder & Equipment Labels
Left-Hand ThreadLH
A notched valve outlet, standard for flammable gases. Physically prevents connecting to A1-only equipment.
Cylinder & Equipment Labels
Recovery CylinderREC
Grey body with a yellow shoulder. Never a disposable cylinder, and never shared between refrigerants.
Cylinder & Equipment Labels
DOT Cylinder StampDOT
Stamped into the collar: specification, service pressure, serial number and the last hydrostatic test date.
Cylinder & Equipment Labels
Retrofit LabelRETRO
Applied after a refrigerant conversion, naming the new refrigerant and oil. Without it the next technician charges the wrong fluid.
Cylinder & Equipment Labels
Equipment Data PlatePLATE
Carries the charge, the refrigerant, MCA, MOCP and the furnace temperature rise range. The authority for that unit.
Symbols vary from one drafter and one set of plans to the next; the legend on the drawing always wins.