On the exam you'll have your NEC Codebook open, and the clock is the enemy. Read each situation, find the NEC section that answers it, and type it in. 50 scenarios to get fast with the index.
What is the maximum number of disconnects allowed for a main service without a main breaker?
All 50 scenarios
What is the maximum number of disconnects allowed for a main service without a main breaker?
NEC 230.71(B)
Section 230.71(B) allows two to six service disconnecting means grouped in one location (the "Rule of Six"). Since the 2020 NEC each must be in its own enclosure or switchboard section, so a panel of six breakers with no main no longer qualifies.
Where are the requirements for grounding electrodes (like ground rods) located?
NEC 250.52
Section 250.52 details the various types of approved grounding electrodes, such as metal water pipe, concrete-encased electrodes (Ufer), and ground rods.
What section covers the spacing requirements for receptacles in a dwelling unit kitchen?
NEC 210.52(C)
Section 210.52(C) outlines the spacing and placement rules for receptacles serving kitchen countertops.
Which table provides the allowable ampacities for insulated conductors (like THHN wire) in a raceway?
NEC Table 310.16
Table 310.16 (formerly 310.15(B)(16)) is the primary table used for determining wire ampacity.
What section covers the working space required in front of electrical equipment?
NEC 110.26
Section 110.26 dictates the depth, width, and height of the clear working space required around electrical equipment.
Where is the requirement for Ground-Fault Circuit-Interrupter (GFCI) protection for personnel located?
NEC 210.8
Section 210.8 lists all the locations (bathrooms, garages, outdoors, etc.) where GFCI protection is mandated.
Which section details the requirements for Arc-Fault Circuit-Interrupter (AFCI) protection?
NEC 210.12
Section 210.12 covers the requirements and locations for AFCI protection in dwelling units and other occupancies.
What section dictates when an ungrounded conductor (white wire) can be used as a hot wire?
NEC 200.7(C)
Section 200.7(C) explains how and when a white or gray conductor can be re-identified and used as an ungrounded conductor.
Where do you find the maximum number of conductors allowed in a standard metal box?
NEC Table 314.16(A)
Table 314.16(A) provides the box volume calculations and maximum conductor fill for standard metal boxes.
What table is used to determine the minimum size for an equipment grounding conductor?
NEC Table 250.122
Table 250.122 is used to size the equipment grounding conductor based on the rating of the overcurrent device protecting the circuit.
Which section strictly limits the number of bends in a run of conduit between pull points?
NEC 358.26
Sections like 358.26 (for EMT) state there shall not be more than the equivalent of four quarter bends (360 degrees total) between pull points.
Where are the rules for supporting and securing Nonmetallic-Sheathed Cable (Romex)?
NEC 334.30
Section 334.30 dictates that NM cable must be supported every 4.5 feet and within 12 inches of every box or enclosure.
What section mandates that all unused openings in electrical boxes and cabinets must be closed?
NEC 110.12(A)
Section 110.12(A) requires that unused openings in boxes, raceways, and cabinets be effectively closed to afford protection equivalent to the wall of the equipment.
Where do you find the requirements for installing a disconnect for a motor?
NEC 430.102
Section 430.102 details the location and requirements for disconnecting means for motors and their controllers.
Which section covers the minimum burial depth for underground wiring?
NEC Table 300.5
Table 300.5 provides the minimum cover requirements (burial depths) for various wiring methods under different conditions.
What section prohibits installing standard receptacles face-up on a kitchen counter?
NEC 406.5(G)
Section 406.5(G) states that receptacles installed on countertop and work surfaces shall not be installed in a face-up position.
Where are the requirements for tamper-resistant (TR) receptacles found?
NEC 406.12
Section 406.12 lists all the areas where 15- and 20-amp, 125-volt and 250-volt nonlocking receptacles must be tamper-resistant.
Which table is used to determine conduit fill capacity?
NEC Chapter 9, Table 1
Chapter 9, Table 1 provides the percentage of cross-sectional area of conduit and tubing permitted for conductors.
What section dictates that splices cannot be made inside a conduit?
NEC 300.15
Section 300.15 requires boxes, conduit bodies, or fittings for all splices and wire terminations; they cannot simply reside inside the pipe.
Where is the rule that mandates a neutral wire at most switch locations?
NEC 404.2(C)
Section 404.2(C) requires a grounded (neutral) conductor to be provided at switch locations to accommodate electronic switches.
What section covers the rules for installing luminaires in clothes closets?
NEC 410.16
Section 410.16 lists the permitted types of luminaires (like fully enclosed surface or recessed) and their required clearances from storage space.
Which section details the continuous load calculation increment (usually 125%)?
NEC 210.20(A)
Section 210.20(A) requires that overcurrent devices be sized at not less than the noncontinuous load plus 125% of the continuous load.
Where are the rules located for wiring swimming pools and similar installations?
NEC Article 680
Article 680 covers the extensive safety, grounding, and bonding requirements for swimming pools, fountains, and hot tubs.
What section protects cords from being used as permanent wiring or run through walls?
NEC 400.12
Section 400.12 list the uses not permitted for flexible cords and cables, including running through walls, ceilings, or as a substitute for fixed wiring.
Where is the table for standard sizes of fuses and circuit breakers?
NEC 240.6(A)
Section 240.6(A) lists the standard ampere ratings for fuses and inverse time circuit breakers (e.g., 15, 20, 25, 30...).
What section handles the requirements for installing a disconnect for an HVAC system?
NEC 440.14
Section 440.14 requires the disconnecting means for air-conditioning equipment to be within sight from and readily accessible from the equipment.
Which section dictates that neutral conductors must not be shared under a single screw in a panel?
NEC 408.41
Section 408.41 requires each grounded (neutral) conductor to terminate within the panelboard in an individual terminal.
Where do you find the rules for calculating the general lighting load of a dwelling?
NEC 220.41
In the 2023 NEC, Section 220.41 gives the dwelling unit general lighting load: 3 volt-amperes per square foot. (Earlier editions put it in Table 220.12, which is still accepted.)
What section covers the color coding for grounded (neutral) conductors?
NEC 200.6
Section 200.6 mandates the means of identifying grounded conductors, generally requiring white, gray, or three continuous white stripes.
Which section requires junction boxes to remain accessible?
NEC 314.29
Section 314.29 states that boxes, conduit bodies, and handhole enclosures must be installed so that wiring can be accessed without removing building finish.
What section covers the rules for temporary wiring on construction sites?
NEC Article 590
Article 590 covers the requirements for temporary electrical power and lighting installations.
Where are the rules for separating Class 2 low-voltage wiring from power/line-voltage wiring?
NEC 725.136(A)
Section 725.136(A) requires separation of Class 2 and Class 3 circuit conductors from those of power and Class 1 circuits.
Which article governs the installation of solar photovoltaic (PV) systems?
NEC Article 690
Article 690 applies to solar PV electrical energy systems, including array circuits, inverters, and charge controllers.
What section prohibits overcurrent devices (breakers/panels) from being located in clothes closets?
NEC 240.24(D)
Section 240.24(D) states overcurrent devices shall not be located in the vicinity of easily ignitable material, such as in clothes closets.
Where do you find the rules regarding the minimum size of service-entrance conductors for a dwelling?
NEC 230.42 / 310.12
Section 230.42 refers to ampacity, and Section 310.12 (formerly 310.15(B)(7)) provides the specific 83% rule for dwelling unit services.
Which section dictates how to properly bond metal water piping systems?
NEC 250.104(A)
Section 250.104(A) outlines the requirements for bonding metal water piping systems to the service equipment enclosure.
What article covers Hazardous (Classified) Locations like gas stations and grain elevators?
NEC Article 500
Article 500 provides the foundation and classification system for areas where fire or explosion hazards may exist.
Where is the rule that mandates "weather-resistant" (WR) receptacles in wet/damp locations?
NEC 406.9(B)(1)
Section 406.9 dictates that all 15- and 20-ampere, 125- and 250-volt nonlocking receptacles in wet and damp locations must be weather-resistant type.
What section provides rules for installing electrical boxes in fire-rated walls?
NEC 300.21
Section 300.21 requires openings around electrical penetrations into or through fire-resistance-rated walls, partitions, floors or ceilings to be firestopped, so the fire rating is kept. The building code sets the ratings themselves.
Which section details the requirement for installing an intersystem bonding termination (IBT) for communications?
NEC 250.94
Section 250.94 requires an intersystem bonding termination (a grounding block) at the service equipment for connecting communications systems (phone/cable).
Where are the rules for sizing equipment grounding conductors when circuit conductors are increased in size?
NEC 250.122(B)
Section 250.122(B) states that if ungrounded conductors are increased in size (usually for voltage drop), equipment grounding conductors must be increased proportionately.
What section covers the rules for running cables through bored holes in wood framing members?
NEC 300.4(A)
Section 300.4(A) requires holes to be bored so the edge of the hole is at least 1 1/4 inches from the edge of the stud, or protected by a steel plate.
Where do you find the table that provides the physical properties (area, resistance) of bare conductors?
NEC Chapter 9, Table 8
Chapter 9, Table 8 provides conductor properties, including circular mil area and DC resistance.
Which section governs the installation of Electric Vehicle (EV) charging systems?
NEC Article 625
Article 625 covers the electrical conductors and equipment exterior to an electric vehicle that connect an electric vehicle to a supply of electricity.
What section dictates that 125-volt, 15- and 20-ampere receptacles installed in dwelling unit basements require GFCI protection?
NEC 210.8(A)(5)
Section 210.8(A)(5) mandates GFCI protection for receptacles in basements. Since the 2020 NEC that covers the whole basement, finished or not.
Where are the rules located for installing ceiling paddle fans directly to an outlet box?
NEC 314.27(C)
Section 314.27(C) details the weight limits and marking requirements for boxes intended to support ceiling-suspended (paddle) fans.
Which section requires a neutral disconnect link or marked terminal at the service equipment?
NEC 230.75
Section 230.75 requires a means to disconnect the grounded (neutral) conductor from the premises wiring, typically a terminal on the busbar.
What article covers generators?
NEC Article 445
Article 445 contains the installation and other requirements for generators.
Where do you find the voltage drop recommendations (informational notes)?
NEC 210.19(A) Informational Note 3
While not a strict rule, 210.19(A) Informational Note 3 suggests keeping voltage drop to 3% for the branch circuit and 5% total.
Which section mandates that lighting fixtures in damp or wet locations must be suitably marked?
NEC 410.10(A)
Section 410.10(A) requires luminaires installed in wet or damp locations to be installed such that water cannot enter, and must be marked "Suitable for Wet Locations" or "Suitable for Damp Locations."