50 cards on the NEC. Turn each one over, then say whether you knew it. The ones you didn't come round again.

Card 1 of 500 knew it · 0 again

Swipe right if you knew it, left to see it again. On a keyboard: Enter turns the card, the arrow keys mark it.

All 50 cards

Wire Sizing

What is the ampacity of a 14 AWG copper conductor at 60°C?
15 Amps
What is the ampacity of a 12 AWG copper conductor at 60°C?
20 Amps
What is the ampacity of a 10 AWG copper conductor at 60°C?
30 Amps
What is the ampacity of a 6 AWG copper conductor at 75°C (THWN)?
65 Amps
What NEC table provides allowable ampacities for insulated conductors?
Table 310.16

Conduit Fill

Max conduit fill for 1 conductor.
53%
Max conduit fill for 2 conductors.
31%
Max conduit fill for 3 or more conductors.
40%
Maximum total degrees of bends between pull points in a conduit run.
360 degrees (equivalent of four quarter bends)
What NEC chapter and table provides conduit fill percentages?
Chapter 9, Table 1

Grounding

What color identifies an equipment grounding conductor?
Green, green with yellow stripes, or bare
What NEC table sizes the equipment grounding conductor?
Table 250.122
What section covers grounding electrode types (ground rods, Ufer, etc.)?
NEC 250.52
Minimum size copper grounding electrode conductor for a 200A service.
4 AWG copper
Section requiring bonding of metal water piping to the service equipment.
NEC 250.104(A)

GFCI/AFCI

NEC section requiring GFCI protection for personnel.
210.8
NEC section requiring AFCI protection.
210.12
Are GFCI receptacles required in bathrooms?
Yes — NEC 210.8(A)(1)
Are AFCI breakers required for bedroom circuits in dwellings?
Yes — NEC 210.12(B)
Name 5 locations requiring GFCI in a dwelling.
Bathrooms, garages, outdoors, crawl spaces, basements

Motors

How is motor branch-circuit conductor sizing calculated?
125% of motor FLC (NEC 430.22)
NEC table for single-phase motor full-load current.
Table 430.248
NEC table for three-phase motor full-load current.
Table 430.250
Max motor branch-circuit short-circuit protection for a standard inverse-time breaker.
250% of motor FLC (NEC 430.52)
Must a motor disconnect be within sight of the motor?
Yes — NEC 430.102(B)

Box Fill

Volume allowance for a 14 AWG conductor in a box fill calculation.
2.00 cubic inches
Volume allowance for a 12 AWG conductor in a box fill calculation.
2.25 cubic inches
How many volume allowances does an internal cable clamp count for?
1 conductor volume (based on largest conductor)
How many volume allowances does a device (switch/receptacle) count for?
2 conductor volumes (based on largest conductor connected)
How many volume allowances does a single equipment grounding conductor count for?
1 conductor volume for up to four EGCs (sized by the largest), plus ¼ volume for each one after that — NEC 314.16(B)(5)

Installation

Minimum depth of working space in front of electrical equipment (Condition 1).
3 feet — NEC 110.26(A)(1)
Minimum width of working space in front of a panel.
30 inches or width of equipment, whichever is greater — NEC 110.26(A)(2)
Can overcurrent devices be installed in clothes closets?
No — NEC 240.24(D)
How far must NM cable be supported from a box?
Within 12 inches — NEC 334.30
Maximum interval for NM cable supports along a run.
Every 4.5 feet — NEC 334.30

Voltage Drop

NEC recommended max voltage drop for a branch circuit.
3% (NEC 210.19(A) Informational Note)
NEC recommended max total voltage drop (feeder + branch).
5% (NEC 215.2(A) Informational Note)
Voltage drop formula for a single-phase circuit.
Vd = (2 × K × I × D) ÷ CM
Value of K (resistivity) for copper conductors.
12.9 ohm-circular mils per foot
Value of K (resistivity) for aluminum conductors.
21.2 ohm-circular mils per foot

Services

Maximum number of service disconnects allowed at one location.
6, each in its own enclosure — NEC 230.71(B) (Rule of Six)
Minimum overhead service clearance over a residential driveway.
12 feet — NEC 230.24(B)(2)
General lighting load per square foot for a dwelling (VA/sf).
3 VA per square foot — NEC 220.41
Continuous load multiplier for overcurrent protection sizing.
125% — NEC 210.20(A)
Section covering color coding of grounded (neutral) conductors.
NEC 200.6 — white, gray, or 3 continuous white stripes

General

What does the NEC define as "Approved"?
Acceptable to the Authority Having Jurisdiction (AHJ)
What is the purpose of the NEC per Article 90?
Safeguard persons and property from hazards arising from the use of electricity
Standard ampere ratings: 15, 20, 25, 30, 35, 40, 45, 50, 60... What section?
NEC 240.6(A)
Section requiring a neutral conductor at most switch locations.
NEC 404.2(C)
Are junction boxes required to remain accessible?
Yes — NEC 314.29