NEC Electrical Exam
Flashcards
50 cards on the NEC. Turn each one over, then say whether you knew it. The ones you didn't come round again.
Card 1 of 500 knew it · 0 again
Swipe right if you knew it, left to see it again. On a keyboard: Enter turns the card, the arrow keys mark it.
All 50 cards
Wire Sizing
- What is the ampacity of a 14 AWG copper conductor at 60°C?
- 15 Amps
- What is the ampacity of a 12 AWG copper conductor at 60°C?
- 20 Amps
- What is the ampacity of a 10 AWG copper conductor at 60°C?
- 30 Amps
- What is the ampacity of a 6 AWG copper conductor at 75°C (THWN)?
- 65 Amps
- What NEC table provides allowable ampacities for insulated conductors?
- Table 310.16
Conduit Fill
- Max conduit fill for 1 conductor.
- 53%
- Max conduit fill for 2 conductors.
- 31%
- Max conduit fill for 3 or more conductors.
- 40%
- Maximum total degrees of bends between pull points in a conduit run.
- 360 degrees (equivalent of four quarter bends)
- What NEC chapter and table provides conduit fill percentages?
- Chapter 9, Table 1
Grounding
- What color identifies an equipment grounding conductor?
- Green, green with yellow stripes, or bare
- What NEC table sizes the equipment grounding conductor?
- Table 250.122
- What section covers grounding electrode types (ground rods, Ufer, etc.)?
- NEC 250.52
- Minimum size copper grounding electrode conductor for a 200A service.
- 4 AWG copper
- Section requiring bonding of metal water piping to the service equipment.
- NEC 250.104(A)
GFCI/AFCI
- NEC section requiring GFCI protection for personnel.
- 210.8
- NEC section requiring AFCI protection.
- 210.12
- Are GFCI receptacles required in bathrooms?
- Yes — NEC 210.8(A)(1)
- Are AFCI breakers required for bedroom circuits in dwellings?
- Yes — NEC 210.12(B)
- Name 5 locations requiring GFCI in a dwelling.
- Bathrooms, garages, outdoors, crawl spaces, basements
Motors
- How is motor branch-circuit conductor sizing calculated?
- 125% of motor FLC (NEC 430.22)
- NEC table for single-phase motor full-load current.
- Table 430.248
- NEC table for three-phase motor full-load current.
- Table 430.250
- Max motor branch-circuit short-circuit protection for a standard inverse-time breaker.
- 250% of motor FLC (NEC 430.52)
- Must a motor disconnect be within sight of the motor?
- Yes — NEC 430.102(B)
Box Fill
- Volume allowance for a 14 AWG conductor in a box fill calculation.
- 2.00 cubic inches
- Volume allowance for a 12 AWG conductor in a box fill calculation.
- 2.25 cubic inches
- How many volume allowances does an internal cable clamp count for?
- 1 conductor volume (based on largest conductor)
- How many volume allowances does a device (switch/receptacle) count for?
- 2 conductor volumes (based on largest conductor connected)
- How many volume allowances does a single equipment grounding conductor count for?
- 1 conductor volume for up to four EGCs (sized by the largest), plus ¼ volume for each one after that — NEC 314.16(B)(5)
Installation
- Minimum depth of working space in front of electrical equipment (Condition 1).
- 3 feet — NEC 110.26(A)(1)
- Minimum width of working space in front of a panel.
- 30 inches or width of equipment, whichever is greater — NEC 110.26(A)(2)
- Can overcurrent devices be installed in clothes closets?
- No — NEC 240.24(D)
- How far must NM cable be supported from a box?
- Within 12 inches — NEC 334.30
- Maximum interval for NM cable supports along a run.
- Every 4.5 feet — NEC 334.30
Voltage Drop
- NEC recommended max voltage drop for a branch circuit.
- 3% (NEC 210.19(A) Informational Note)
- NEC recommended max total voltage drop (feeder + branch).
- 5% (NEC 215.2(A) Informational Note)
- Voltage drop formula for a single-phase circuit.
- Vd = (2 × K × I × D) ÷ CM
- Value of K (resistivity) for copper conductors.
- 12.9 ohm-circular mils per foot
- Value of K (resistivity) for aluminum conductors.
- 21.2 ohm-circular mils per foot
Services
- Maximum number of service disconnects allowed at one location.
- 6, each in its own enclosure — NEC 230.71(B) (Rule of Six)
- Minimum overhead service clearance over a residential driveway.
- 12 feet — NEC 230.24(B)(2)
- General lighting load per square foot for a dwelling (VA/sf).
- 3 VA per square foot — NEC 220.41
- Continuous load multiplier for overcurrent protection sizing.
- 125% — NEC 210.20(A)
- Section covering color coding of grounded (neutral) conductors.
- NEC 200.6 — white, gray, or 3 continuous white stripes
General
- What does the NEC define as "Approved"?
- Acceptable to the Authority Having Jurisdiction (AHJ)
- What is the purpose of the NEC per Article 90?
- Safeguard persons and property from hazards arising from the use of electricity
- Standard ampere ratings: 15, 20, 25, 30, 35, 40, 45, 50, 60... What section?
- NEC 240.6(A)
- Section requiring a neutral conductor at most switch locations.
- NEC 404.2(C)
- Are junction boxes required to remain accessible?
- Yes — NEC 314.29