NEC Electrical Exam
Myth vs code
50 things electricians hear on the job, each checked against the NEC, with the section that settles it.
What you hear
You can use the white wire in a Romex cable as a hot wire without marking it.
All 50 myths
You can use the white wire in a Romex cable as a hot wire without marking it.
If a white wire is used as an ungrounded (hot) conductor, such as in a switch loop or 240V circuit, it must be permanently reidentified (usually with black or red tape) at all terminations and splices.
NEC 200.7(C)
Romex (NM-B) cable can be installed in outdoor conduit.
NM-B cable is strictly for dry, indoor locations. The inside of an outdoor conduit is considered a wet location, requiring conductors like THWN or UF cable.
NEC 334.12 / 300.9
A single grounding rod is always enough for a residential service.
A single ground rod must have a resistance to earth of 25 ohms or less. Since this is hard to prove without specialized equipment, a second ground rod driven at least 6 feet apart is almost always installed to bypass the 25-ohm requirement.
NEC 250.53(A)(2)
You don't need GFCI protection for a refrigerator in a garage or kitchen.
All 125-volt, single-phase, 15- and 20-ampere receptacles installed in garages and kitchens must have GFCI protection. There are no longer exceptions for dedicated appliances like refrigerators or freezers in these locations.
NEC 210.8(A)(2) / 210.8(A)(6)
Romex stapled perpendicular across the bottom of floor joists in a basement is acceptable.
Where NM cable runs across the bottom of floor joists in an unfinished basement, it must go through bored holes or on running boards. Only cables with at least two 6 AWG or three 8 AWG conductors may be stapled directly to the bottom of the joists.
NEC 334.15(C)
Every junction box must be readily accessible, out in the open where you can reach it without tools.
Boxes must be accessible, not readily accessible. You may have to take off a cover or lift out a ceiling tile to reach one, but you must never have to remove part of the building or its finish, so a box can't be buried behind drywall or paneling.
NEC 314.29
A subpanel in a detached garage requires a main breaker.
A detached garage fed by a feeder needs a disconnecting means where the feeder enters, but it can be up to six switches or breakers grouped together (NEC 225.33). A single main breaker is only needed when there would be more than six.
NEC 225.33
You can bond the neutral to the ground in a subpanel.
The neutral and grounding conductors must be strictly separated in all subpanels. They are only bonded together at the main service equipment.
NEC 250.24(A)(5)
Any outlet installed in a bathroom must be on a dedicated 20-amp circuit.
Bathroom receptacle outlets must be supplied by at least one 20-amp branch circuit. This circuit can supply multiple bathrooms, or it can supply other loads (like lights/fans) but *only* within that single bathroom.
NEC 210.11(C)(3)
Low-voltage wiring (like thermostat or doorbell wire) can be run in the same conduit as 120V wiring.
Class 2 and Class 3 low-voltage wiring must not be placed in the same conduit, enclosure, or raceway as light or power conductors, unless separated by a barrier.
NEC 725.136(A)
Electrical panels can be installed in a closet if it's large enough.
Overcurrent devices (panels) are strictly prohibited from being located in the vicinity of easily ignitable material, such as in clothes closets.
NEC 240.24(D)
You can use the grounding conductor (green/bare wire) as a neutral if needed.
The equipment grounding conductor is only intended to carry fault current, never normal operating current. Using it as a neutral creates a dangerous shock hazard by putting current on metal device frames.
NEC 250.142(B)
AFCI protection is only required in bedrooms.
AFCI protection was expanded long ago. It is now required in nearly all habitable rooms of a dwelling unit, including family rooms, dining rooms, living rooms, kitchens, and hallways.
NEC 210.12(B)
Underground PVC conduit doesn't need to be glued if it fits tightly.
All PVC conduit joints must be made using approved solvent cement to ensure they are watertight and mechanically secure.
NEC 352.48
You can double-tap neutral wires under a single screw in a panel busbar.
Each grounded (neutral) conductor within a panelboard must terminate in an individual terminal that is not used for any other conductor.
NEC 408.41
A 15-amp receptacle cannot be installed on a 20-amp circuit.
Multiple 15-amp receptacles can be installed on a 20-amp general-purpose branch circuit. A single 15-amp receptacle (like a single outlet for a dedicated appliance) cannot be the only plug on a 20-amp circuit.
NEC Table 210.21(B)(3)
A kitchen island must always have at least one receptacle outlet.
Recent code changes (2023 NEC) no longer mandate a receptacle on an island. If one is installed, it must meet specific location requirements, or provisions for future receptacles must be made.
NEC 210.52(C)(2)
It's fine to use indoor wire nuts outside if you tape them up well.
Wire connectors used in wet locations must be specifically listed for wet locations, typically filled with a silicone sealant to prevent corrosion.
NEC 314.30(C) / 110.14(B)
Conduit fill capacity is 50% for all conduit types and wire counts.
For three or more conductors in a conduit, the maximum fill capacity is 40% of the cross-sectional area. For two conductors, it's 31%, and for a single conductor, it's 53%.
NEC Chapter 9, Table 1
You can support Romex (NM cable) using the plumbing pipes running parallel to it.
Cables and raceways must be securely fastened in place by supports made for the purpose. A plumbing pipe isn't one: NM cable is secured with staples, cable ties or straps designed for it, at the spacings in 334.30.
NEC 300.11(A) / 334.30
A ceiling fan can be hung from any standard light fixture ceiling box.
Ceiling fans must be supported by outlet boxes listed and marked for the sole support of ceiling-suspended (paddle) fans, unless supported directly by the building structure.
NEC 314.27(C)
Direct burial cable (UF) only needs to be buried 12 inches deep everywhere.
Direct burial cable generally needs 24 inches of cover. It can be 12 inches for a residential 120-volt circuit of 20 amps or less with GFCI protection, or 18 inches under a one- or two-family dwelling's driveway. Under a building it must be in a raceway.
NEC Table 300.5
All metal pipes inside a house must be bonded to the electrical system.
Metal water piping systems and structural metal must be bonded. Other metal piping (like gas lines) is generally considered bonded if connected to an appliance grounded by an equipment grounding conductor.
NEC 250.104(A), (B) & (C)
You can splice a wire inside a conduit if the conduit is large enough.
Splices are prohibited inside conduits and raceways. All splices must be made within an approved enclosure, junction box, or conduit body with a removable cover.
NEC 300.15
The NEC requires smoke detectors in every room.
The NEC dictates *how* smoke detectors are wired (power source, interconnection), but the building code (like IRC or local fire codes) determines *where* they must be located.
NEC 760 (Fire Alarms) / NFPA 72
A 240V water heater requires a neutral wire.
A standard residential electric water heater is a pure 240V load and requires two hot wires and a ground. It does not use a neutral.
NEC Article 422
You can run a cord permanently through a wall or ceiling instead of installing an outlet.
Flexible cords and cables shall not be used as a substitute for the fixed wiring of a structure, nor run through holes in walls, ceilings, or floors.
NEC 400.12
Pigtailing is mandatory for all receptacle installations.
Pigtailing is only strictly required for the neutral (grounded) conductor on multiwire branch circuits. Otherwise, looping through device terminals is permitted, though many electricians prefer pigtailing.
NEC 300.13(B)
An electrical panel must have at least 30 inches of clearance in front of it.
A panel requires a clear working space 30 inches wide (or width of the equipment, whichever is greater), extending 36 inches deep in front of the panel, and up to 6.5 feet high.
NEC 110.26(A)
Tamper-resistant (TR) receptacles are only required in children's bedrooms.
TR receptacles are required in nearly all areas of a dwelling unit, including garages, outdoors, and general living spaces.
NEC 406.12
Any disconnect switch for an AC unit can be installed directly behind the unit.
The disconnecting means must be readily accessible and within sight from (visible and not more than 50 feet from) the air-conditioning equipment, and the working space in front of the disconnect cannot be blocked.
NEC 440.14
You must use anti-oxidant paste on all aluminum wire connections.
Anti-oxidant paste is only required if the manufacturer of the terminal or connector specifically requires it, though it is often considered a good practice for larger aluminum stranded cables.
NEC 110.14
Any light fixture can be installed above a bathtub or shower.
Luminaires installed within the tub/shower zone (3 feet horizontally and 8 feet vertically from the threshold) must be listed for damp locations, or wet locations if subject to shower spray. No cord-connected fixtures or ceiling fans are allowed in this zone.
NEC 410.10(D)
Switches are allowed to disconnect the neutral wire instead of the hot wire.
Switches must only disconnect the ungrounded (hot) conductor. Switching the neutral leaves the appliance or light fixture continuously energized with respect to ground, creating a severe shock hazard.
NEC 404.2(B)
Buried warning tape over underground electrical lines is optional.
For service conductors not encased in concrete and buried 18 inches or deeper, a warning ribbon must be placed in the trench at least 12 inches above the underground installation.
NEC 300.5(D)(3)
Receptacles can be mounted face-up on a kitchen countertop.
Receptacle assemblies for countertop applications shall not be installed in a face-up position unless specifically listed for the application (like pop-up assemblies). Regular outlets will collect water and debris.
NEC 406.5(G)
You can use 14 AWG wire for a 20-amp circuit as long as the load is small.
The branch circuit overcurrent device determines the required wire size. A 20-amp breaker requires a minimum of 12 AWG copper wire. You cannot protect 14 AWG wire with a 20-amp breaker for general use.
NEC 240.4(D)
A ground fault circuit interrupter (GFCI) is the same thing as an arc fault circuit interrupter (AFCI).
They serve different purposes. A GFCI protects against shock by detecting small imbalances in current (ground faults). An AFCI protects against fire by detecting dangerous arcing conditions in the wiring.
NEC Article 100 Definitions
Extension cords can be stapled to baseboards to keep them tidy.
Flexible cords cannot be attached to building surfaces, concealed behind walls or ceilings, or subject to physical damage.
NEC 400.12
If a house has old two-prong outlets with no ground wire, you must rewire the whole house to install three-prong outlets.
You can replace a two-prong outlet with a GFCI outlet (or a standard three-prong outlet protected by an upstream GFCI) if marked "No Equipment Ground." It protects against shock, though it doesn't create a true ground.
NEC 406.4(D)(2)
Electrical tape can be used as the sole method to cap off unused wires in a junction box.
Wire ends must be terminated in a listed wire connector (like a wire nut) or other approved means. Tape alone is not an approved mechanical termination for live or neutral wire ends.
NEC 110.14
Receptacles must always be installed with the ground pin facing up.
The NEC does not specify which way the ground pin must face. It’s entirely a matter of preference or local specification, though both orientations have valid arguments for safety.
No NEC Reference specifying orientation
Outdoor receptacles only require a weather-resistant cover when they are not in use.
Receptacles in wet locations where the receptacle is exposed to weather must have an enclosure that is weatherproof whether or not the attachment plug is inserted (often called an "in-use" cover).
NEC 406.9(B)(1)
A subpanel neutral bus bar must be bonded to the metal enclosure.
The neutral bus bar in a subpanel must be rigidly isolated from the metal enclosure to prevent the enclosure from carrying return current. Only the ground bus is bonded to the enclosure.
NEC 250.24(A)(5)
Metal boxes do not need to be grounded if you are using plastic Romex (NM) cable.
Metal boxes must always be grounded. The bare grounding wire from the NM cable must be attached to the metal box using an approved grounding screw or clip.
NEC 250.148
You don't need a neutral wire at a switch box if the switch just controls a basic light.
The 2011 NEC began requiring a neutral (grounded) conductor at most switch locations to accommodate modern electronic switches (like smart switches and occupancy sensors) that require standby power.
NEC 404.2(C)
MC cable armor can serve as the primary equipment ground.
Standard interlocking armor MC (Metal-Clad) cable cannot serve as the sole equipment grounding conductor; it contains a dedicated green wire for this. (AC cable or Healthcare Facility MC cable is different).
NEC 330.108 / 250.118(10)
It's safe to combine the grounds and neutrals under the same screw terminal on a main panel bus.
Each neutral wire must have its own dedicated terminal. Ground wires can sometimes share terminals depending on the panel manufacturer's instructions, but never mixed with neutrals in the same hole.
NEC 408.41
Liquidtight Flexible Metal Conduit (LFMC) can be used anywhere standard EMT is used.
While highly versatile, LFMC has restrictions. Among them, it cannot be used where subject to physical damage, and limitations exist on lengths when relied upon as an equipment grounding conductor.
NEC 350.12
If a circuit breaker trips frequently, installing a larger breaker is an acceptable fix.
A breaker is sized to protect the wire. Increasing the breaker size without increasing the wire size removes the protection, allowing the wire to overheat and potentially cause a fire.
NEC 240.4