IPC Plumbing Exam
Myth vs code
50 things plumbers hear on the job, each checked against the IPC, with the section that settles it.
What you hear
You can use a sanitary tee on its back for horizontal-to-horizontal drainage changes of direction.
All 50 myths
You can use a sanitary tee on its back for horizontal-to-horizontal drainage changes of direction.
Sanitary tees are strictly for vertical-to-horizontal drainage. Using them on their backs causes turbulent flow and clogs. You must use a wye and 1/8 bend, or a combination wye and 1/8 bend (combo) for horizontal-to-horizontal drainage.
IPC Table 706.3
Vent pipes don't need slope; they just carry air.
The code says vent and branch vent pipes must be graded and connected so they drain back to the drainage pipe by gravity. Moisture condenses inside vents, and that slope lets it run back down instead of collecting and blocking the vent.
IPC 905.2
A 1/4 inch per foot slope is always the best for all drainage pipe sizes.
While 1/4" per foot is standard for pipes 2½ inches or smaller, larger pipes require less slope to maintain the correct flow velocity (to keep solids suspended). Pipes 3 to 6 inches require 1/8" per foot.
IPC Table 704.1
You can discharge a water heater temperature and pressure (T&P) relief valve directly into the drainage system.
T&P relief valves must discharge through an air gap into an indirect waste receptor, or to the outdoors. Direct connection risks sucking sewage back into the potable water supply during a pressure drop.
IPC 504.6 / 802.1
A trap primer is only needed on floor drains that see frequent use.
It's exactly the opposite. Trap primers (or deep seal traps) are required for emergency floor drains or drains that *don't* see regular use, to prevent the trap seal from evaporating and letting sewer gas into the building.
IPC 1002.4
It's acceptable to notch the bottom of a load-bearing joist to run a 2-inch drain pipe if it's less than half the joist depth.
Notches in the top or bottom of joists cannot exceed 1/6 of the joist depth and cannot be located in the middle third of the span. Holes must be at least 2 inches from the top or bottom edge.
IRC R502.8.1
S-traps are perfectly fine to use under a kitchen or bathroom sink.
S-traps are strictly prohibited in modern plumbing. They are highly susceptible to self-siphoning, which drains the water seal and allows toxic sewer gases to enter the home. A P-trap with proper venting must be used instead.
IPC 1002.3
You can use a double sanitary tee cross fitting for back-to-back water closets (toilets).
Unless the water closets are discharging into an oversized pipe or spaced at specific distances, double sanitary tees cannot be used for back-to-back blowout fixtures. A double wye or figure-8 fitting is required to prevent waste from blowing across the fitting into the opposing drain.
IPC 706.3
You can use any convenient pipe size for a vent.
Vents are strictly regulated strictly by fixture units (DFUs) and developed length. The minimum size for any vent is 1-1/4 inches, and an individual vent must be at least half the diameter of the drain it serves.
IPC 906.1
Fixtures don't need dedicated vents if they are close enough to the main stack.
While stack venting is allowed in certain configurations, every trap must have a protecting vent. The maximum developed distance from the trap weir to the vent connection depends on pipe size and slope, and strictly cannot be exceeded.
IPC 909.1
Cleanouts aren't needed if a pipe runs in a perfectly straight line.
Code requires cleanouts on horizontal drains at maximum intervals of 100 feet. Additionally, a cleanout is required for every change of direction greater than 45 degrees.
IPC 708.1.1 / 708.1.4
A quarter bend (90-degree elbow) is perfectly acceptable for horizontal-to-horizontal drainage.
Standard 90-degree bends (quarter bends) are only allowed for vertical-to-horizontal or horizontal-to-vertical directions. For horizontal-to-horizontal drainage, you must use a long sweep quarter bend to prevent clogging.
IPC Table 706.3
Galvanized steel pipe can be directly threaded into copper fittings.
Connecting dissimilar metals (like steel/iron and copper) directly cases galvanic corrosion, drastically reducing the lifespan of the pipe. A dielectric union or a brass adapter must be used to isolate the metals.
IPC 605.23.1
Plumbing fixtures connecting directly to the central drainage system do not always need to be trapped.
Every plumbing fixture must be separately trapped by a liquid-seal trap. The trap prevents foul, toxic, and explosive sewer gases from escaping the piping system into the building.
IPC 1002.1
A dishwasher drain hose can be connected straight to the garbage disposal drain without any loop.
The dishwasher drain must have a high loop secured under the counter, or be routed through a countertop air gap fitting. This prevents wastewater from the sink backing up into the clean dishwasher compartment.
IPC 802.1.6
Air Admittance Valves (AAVs) can be used anywhere a standard vent is difficult to install.
AAVs have specific limitations. They must be installed installed upright, remain accessible for maintenance, and cannot be used to vent sumps, chemical waste, or areas subject to positive sewer pressures.
IPC 918
Any standard PVC glue (solvent cement) works on all plastic plumbing pipes.
Different plastics require specific solvent cements tested for their chemical composition. PVC, CPVC, and ABS all require their own distinct primers and cements to create a chemical weld that complies with code safety standards.
IPC 605
Water piping can be run freely through unheated attics to save space.
All water pipes installed in areas subject to freezing temperatures (like unheated attics or crawlspaces) must be protected with adequate insulation or heat trace wire to prevent freezing and bursting.
IPC 305.4
PEX piping can be left exposed to sunlight indefinitely on the side of a house.
PEX (cross-linked polyethylene) is highly vulnerable to degradation from Ultraviolet (UV) light. PEX must be protected from direct and indirect sunlight, typically stored in dark bags and installed strictly indoors or underground.
IPC 305.8
Water heaters can be installed directly on the floor in residential garages.
Unless the water heater is designated as Flammable Vapor Ignition Resistant (FVIR), its ignition source (burner or element) must be elevated at least 18 inches above the garage floor to avoid igniting heavy flammable vapors from vehicles or stored chemicals.
IPC 502.1 / IFGC 305.3
Underground plastic gas piping requires no special treatment once buried.
Non-metallic underground gas piping (like yellow PE) must be installed with an electrically continuous yellow insulated copper tracer wire laid alongside it. This allows locators to find the pipe from the surface and prevent accidental strikes.
IFGC 404.17.3
Sewer gas is harmless, it just has a bad smell.
Sewer gas is highly dangerous. It contains a mixture of toxic and explosive gases, including hydrogen sulfide (H2S) and methane. This is the primary reason why P-traps and venting systems are strictly mandated by code.
General Safety / IPC Chapter 10
Standard rubber Fernco (flexible) couplings are approved for above-ground plumbing repairs inside a building.
Standard all-rubber mechanical couplings are for underground use only. Above-ground use requires shielded couplings (encased in a full metallic shear band) to maintain pipe alignment and prevent collapse during a fire or structural shift.
IPC 705.16
A fixture tailpiece connecting the sink drain to the trap can be as long as you want.
To prevent the momentum of falling water from siphoning the trap dry, the vertical distance from the fixture outlet to the trap weir cannot exceed 24 inches in most standard residential applications.
IPC 1002.1
Toilets (water closets) can be installed snugly against a vanity or wall to save space.
Codes mandate strict clearances for accessibility and comfort. A water closet must have a minimum clearance of 15 inches from its center to any side wall or obstruction, and a minimum of 21 inches of clearance in front of it.
IPC 405.3.1
A shower pan liner only needs to cover the flat subfloor before pouring the sloped mortar bed.
The shower pan liner itself must be sloped at 1/4 inch per foot toward the weep holes of the drain *before* the top mortar bed is applied. If the liner is flat, water will pool underneath the tile and cause stagnant odors and rot.
IPC 417.5.2
The temperature of hot water going to a bathtub doesn't need to be limited if the user controls the handles.
Bathtub and whirlpool tub valves must be equipped with an ASSE 1070 compliant mixing valve or temperature limiting device set to deliver water at a maximum of 120°F to prevent severe scalding.
IPC 412.3
Potable water service pipes and sewer pipes can be buried touching each other in the same trench.
To prevent contamination of drinking water if a leak occurs, the water service pipe must be separated from the sewer by at least 5 feet of undisturbed earth. If run in the same trench, the water pipe must be sleeved or shelved at least 12 inches higher than the sewer line.
IPC 603.2
A washing machine standpipe can be made from 1-1/2 inch PVC.
Modern high-efficiency washing machines pump out water extremely fast. Current codes require the standpipe, trap, and the drain it discharges into to be a minimum of 2 inches in diameter to handle the flow without overflowing.
IPC 406.2
A washing machine standpipe only needs to be a few inches tall.
To prevent suds and water from overflowing, the standpipe the washing machine hose dumps into must be a minimum of 18 inches and a maximum of 42 inches above the trap weir.
IPC 802.4.3
Roof vents can terminate completely flush with the roof shingles for better aesthetics.
Vents must extend at least 6 inches above the roof surface to prevent snow, leaves, or water from blocking the pipe. Furthermore, they must be situated at least 10 feet horizontally or 3 feet vertically from openable windows or air intakes.
IPC 904.1 / 904.5
A kitchen sink's P-trap can be installed below the floor level (in a crawlspace or basement).
The trap must be installed in the same room and directly below the fixture it serves to remain accessible for cleaning out clogs and retrieving dropped items.
IPC 1002.1
Standard DWV (Drain, Waste, Vent) PVC fittings can be used to route cold water supply lines.
DWV fittings are absolutely prohibited for pressurized water supplies. They do not have the deeper socket depth or pressure rating required to handle the standard 40-80 PSI of a potable water system and will eventually burst.
IPC 605
All pipes expand under heat at roughly the same rate, so you strap them the exact same way.
Plastic pipes like PVC, CPVC, and PEX expand significantly more than metallic copper or steel when exposed to hot water. Specific expansion loops, offsets, and loose hangers must be used so the plastic pipe doesn't buckle and break under thermal stress.
IPC 305.2
Private septic systems work indefinitely without being emptied.
Proper maintenance protocols (often adopted as local ordinance) require septic tanks to be systematically pumped out every 3 to 5 years. Solid sludge accumulates over time and will overflow into the leach field, destroying it entirely.
EPA Guidelines / Local Codes
Purple primer and PVC cement can be applied exactly the same way in freezing weather.
Standard solvent cements take much longer to cure in temperatures below 40°F. Plumbers must use specialized cold-weather cements, store them warm, and allow significantly longer set times before pressure testing.
Manufacturer ASTM Specs / IPC 605.14.2
The T&P relief valve discharge tube can just empty into the water heater's required leak pan.
The T&P discharge pipe must terminate to an independent air gap or to the outdoors. Directing it into the water heater leak pan is prohibited because the fast-moving, scalding water from a blow-off would completely overflow the shallow pan.
IPC 504.6
Bathroom exhaust fans can legally vent the humid air directly into a ventilated attic.
Bathroom exhaust fans must duct directly to the outside of the building. Venting warm, moist air into an attic leads almost immediately to severe condensation, rot, and toxic mold growth across the roof trusses.
IRC M1501.1
A wet vent system can branch out and horizontally vent the whole house.
Horizontal wet venting is typically restricted to serving fixtures within a single bathroom group. You cannot legally wet vent fixtures from a kitchen or laundry room into a distant bathroom's piping system.
IPC 912.1
Crown venting (connecting the vent immediately behind the peak of the trap) is a great space-saver.
Crown venting is prohibited. The vent connection must be installed a distance of at least two pipe diameters away from the trap weir. Placing it too close causes turbulent wastewater to wash up into the vent, eventually clogging it with grease and debris.
IPC 905.5
Food waste grinders (disposals) in commercial kitchens should run through the grease interceptor to catch the food.
Food waste grinders should never discharge into a standard grease interceptor. The heavy solids will quickly fill the interceptor, rendering it unable to separate grease and violating its operational design.
IPC 1003.3.2
A water service pipe coming from the street can be made of any material as long as it holds water.
The water service pipe must be strictly manufactured of approved potable water materials (like Copper, PEX, CPVC, or HDPE), and its installation must maintain the safety of the drinking water supply.
IPC 605.3
It is not necessary to have a cleanout at the base of every multi-story drainage stack.
A cleanout is explicitly required at the base of each waste or soil stack. This allows plumbers to clear massive vertical blockages safely without cutting the pipe open while it is full of pressure and sewage.
IPC 708.1.3
The building sewer pipe leaving the house can be smaller than the building drain pipe inside.
Pipes carrying gravity drainage can never decrease in size in the direction of flow. The building sewer must be sized properly and at minimum be the exact same diameter as the building drain connecting to it.
IPC 710.1
Island sinks don't need to be vented because they are isolated.
Every trap must be vented. For kitchen island sinks where a standard vertical vent cannot go up through the ceiling, code permits a specialized "island fixture vent" loop extending as high as possible under the counter, or the use of an Air Admittance Valve (if local jurisdiction allows).
IPC 913 / 918
Test plugs used to block pipes during air or water tests just need to be tightened snugly; bracing is overkill.
Test plugs must always be braced or secured. A standard 4-inch pipe under 5 PSI of air test pressure exerts over 60 pounds of force against the plug. If it blows out, it becomes a deadly projectile.
General Safety / OSHA Standard
Vacuum breakers are only required for commercial mop sinks or industrial hoses.
Hose bibb vacuum breakers are required on all residential sillcocks and outdoor faucets. They prevent back-siphonage of contaminated water (like standing water in a garden puddle or chemical fertilizer sprayer) back into the home's drinking supply when system pressure drops.
IPC 608.15.4
Lead pipe and lead solder can still be used for minor repairs in older homes that already have lead piping.
The Safe Drinking Water Act and plumbing codes strictly prohibit the use of lead pipes, lead solder, or lead fixtures in any potable water supply system, regardless of the age or existing materials of the house structure.
IPC 605.2
Corrugated Stainless Steel Tubing (CSST) for natural gas can be installed just like standard black iron pipe.
CSST has special requirements, the most critical being that it must be directly bonded to the electrical service grounding electrode system. Due to its thin walls, if struck by a lightning arc without proper grounding, it will melt, explode, and cause catastrophic fire.
IFGC 310.1.1
Water hammer arrestors are a luxury addition only needed for noisy pipes in large houses.
Water hammer arrestors are legally required wherever quick-closing valves are installed (such as near washing machines, dishwashers, and icemakers). Fast-acting solenoid valves cause violent hydraulic shockwaves that can fracture fittings if not absorbed.
IPC 604.9