Code tables · 3 of 10
Building Drain & Sewer Sizing
IPC Table 710.1(1)
Maximum number of DFUs that may be connected to a building drain based on slope.
| Pipe Size (Inches) | 1/16" Slope | 1/8" Slope | 1/4" Slope |
|---|---|---|---|
| 1 1/4" | - | - | 1 |
| 1 1/2" | - | - | 3 |
| 2" | - | - | 21 |
| 2 1/2" | - | - | 24 |
| 3" | - | 36 | 42 |
| 4" | - | 180 | 216 |
| 5" | - | 390 | 480 |
| 6" | - | 700 | 840 |
| 8" | 1,400 | 1,600 | 1,920 |
| 10" | 2,500 | 2,900 | 3,500 |
Check the figures against the edition of the IPC/UPC Codebook your exam uses; local amendments can change them.