Hanger and Support Spacing
IPC Table 308.5
Maximum horizontal and vertical spacing for pipe supports.
| Piping Material | Max Horizontal | Max Vertical |
|---|---|---|
| ABS Pipe | 4 feet | 10 feet |
| Aluminum Tubing | 10 feet | 15 feet |
| Cast-Iron Pipe | 5 feet | 15 feet |
| Copper or Copper-Alloy (≤ 1 1/4") | 6 feet | 10 feet |
| Copper or Copper-Alloy (≥ 1 1/2") | 10 feet | 10 feet |
| CPVC Pipe or Tubing (≤ 1") | 3 feet | 10 feet |
| CPVC Pipe or Tubing (≥ 1 1/4") | 4 feet | 10 feet |
| PEX Tubing (≤ 1") | 32 inches | 10 feet |
| PVC Pipe | 4 feet | 10 feet |
| Steel Pipe | 12 feet | 15 feet |
Check the figures against the edition of the IPC/UPC Codebook your exam uses; local amendments can change them.