Trap-to-vent distances and vent sizing from the model code. Your local amendments override every line of it — check before you rough in.
Max trap-to-vent distance
IPC Table 909.1
| Trap | Max distance | Min vent |
|---|---|---|
| 1¼" | 5 ft | 1¼" |
| 1½" | 6 ft | 1¼" |
| 2" | 8 ft | 1½" |
| 3" | 12 ft | 2" |
| 4" | 16 ft | 3" |
Measured from the trap weir to the inner edge of the vent pipe opening.
Vent sizing by DFU and length
IPC Table 906.1
| Drain | DFU | Vent | Max length |
|---|---|---|---|
| 1½" | 1 | 1¼" | 45 ft |
| 1½" | 8 | 1½" | 60 ft |
| 2" | 12 | 1½" | 75 ft |
| 2" | 20 | 2" | 150 ft |
| 3" | 10 | 1½" | 42 ft |
| 3" | 30 | 2" | 150 ft |
| 3" | 60 | 3" | 300 ft |
| 4" | 100 | 2" | 75 ft |
| 4" | 200 | 3" | 180 ft |
| 4" | 500 | 4" | 390 ft |
Developed length is measured from the vent connection to open air.
Rules of thumb
- A vent is at least half the drain size, and never smaller than 1¼".
- An individual vent connects within two pipe diameters of the trap weir.
- Wet venting is allowed for a bathroom group on one floor level.
- A terminal extends at least 6" above the roof and stays 10 ft clear of any air intake.
- Island venting needs a loop rising above the flood rim.