Trap-to-vent distances and vent sizing from the model code. Your local amendments override every line of it — check before you rough in.

Max trap-to-vent distance

IPC Table 909.1

TrapMax distanceMin vent
1¼"5 ft1¼"
1½"6 ft1¼"
2"8 ft1½"
3"12 ft2"
4"16 ft3"

Measured from the trap weir to the inner edge of the vent pipe opening.

Vent sizing by DFU and length

IPC Table 906.1

DrainDFUVentMax length
1½"11¼"45 ft
1½"81½"60 ft
2"121½"75 ft
2"202"150 ft
3"101½"42 ft
3"302"150 ft
3"603"300 ft
4"1002"75 ft
4"2003"180 ft
4"5004"390 ft

Developed length is measured from the vent connection to open air.

Rules of thumb

  • A vent is at least half the drain size, and never smaller than 1¼".
  • An individual vent connects within two pipe diameters of the trap weir.
  • Wet venting is allowed for a bathroom group on one floor level.
  • A terminal extends at least 6" above the roof and stays 10 ft clear of any air intake.
  • Island venting needs a loop rising above the flood rim.