Skip to content

Myth vs code

25 things water operators hear on the job, each checked against the ABC formula sheet, the federal drinking water rules and good operating practice, with the source that settles it.

Myth 1 of 25

What you hear

Use 7.48 to convert flow and dose into pounds per day.

All 25 myths

  1. Use 7.48 to convert flow and dose into pounds per day.

    7.48 converts cubic feet to gallons. Pounds use 8.34, the weight of one gallon of water.

    ABC Formula Sheet - Parts per Million / Pounds

  2. CT is calculated from the chlorine dose applied.

    CT uses the residual measured at the end of the contact chamber. The dose includes chlorine the water already consumed.

    Surface Water Treatment Rule

  3. High pH means high alkalinity.

    pH is intensity, alkalinity is capacity. A water can sit at pH 9 with almost no ability to resist an acid addition.

    Water Chemistry

  4. Chlorine disinfects better as pH rises.

    It gets worse. Higher pH shifts chlorine to the weaker hypochlorite ion, so required CT increases.

    Disinfection

  5. Mud balls in a filter mean you backwashed too hard.

    They mean the opposite. Inadequate washing lets floc and media bind together into hardened balls.

    Filtration

  6. A positive Langelier Index means the water is corrosive.

    Positive is scale forming. Negative is corrosive. Reversing the sign reverses every conclusion you draw.

    Corrosion Control

  7. Alum raises the pH of the water it is added to.

    Alum is acidic. It consumes alkalinity and lowers pH, most sharply in poorly buffered water.

    Coagulation

  8. Brake horsepower is less than water horsepower.

    It is always greater. Efficiency losses mean the shaft must supply more than reaches the water.

    Pumping

  9. Cavitation is caused by too much discharge pressure.

    It is a suction side problem. Suction pressure falling below vapour pressure forms the bubbles.

    Pumping

  10. MCL and MCLG are two names for the same limit.

    MCL is the enforceable legal ceiling. MCLG is a health goal set with no regard to cost or feasibility.

    Safe Drinking Water Act

  11. Hardness and alkalinity measure the same thing.

    Hardness is calcium and magnesium. Alkalinity is carbonate and bicarbonate. They only share the unit.

    Water Chemistry

  12. Flush the tap before taking a lead and copper sample.

    Lead and copper samples are first draw, after at least six hours standing. Flushing removes the very water being tested.

    Lead and Copper Rule

  13. Rapid mix is where floc grows into settleable particles.

    Rapid mix only disperses the coagulant. Floc grows during slow flocculation that follows.

    Coagulation

  14. A longer detention time always means better settling.

    Only if the basin is not short circuiting. Actual flow paths matter more than the calculated average.

    Sedimentation

  15. Groundwater never needs filtration.

    Groundwater under the direct influence of surface water is regulated as surface water and must be filtered, unless the state grants filtration avoidance.

    Surface Water Treatment Rule

  16. Detention time in hours is volume divided by flow in MGD.

    Not directly. Convert MGD to gallons per hour first, or you will be out by a factor of 24.

    ABC Formula Sheet - Detention Time

  17. A vault that has been open all morning is safe to enter.

    Atmosphere must be tested immediately before every entry. Heavier-than-air gases settle back regardless of how long it stood open.

    Confined Space Entry

  18. Soap solution is the way to find a chlorine gas leak.

    Ammonia vapour is. It reacts with chlorine to make a visible white cloud; soap does not react at all.

    Chlorine Safety

  19. Total dynamic head is static head minus friction losses.

    Losses add. TDH is static head plus friction and velocity losses, because the pump must overcome all of them.

    Pumping

  20. Multiply by 17.1 to convert mg/L hardness into grains per gallon.

    Divide. 17.1 mg/L equals one grain per gallon, so 171 mg/L is 10 gpg, not 2,924.

    ABC Formula Sheet - Conversions

  21. Turbidity and total dissolved solids measure the same thing.

    Turbidity is suspended material that scatters light. TDS is dissolved material that passes a filter entirely.

    Water Chemistry

  22. A filter run should always be ended on a fixed schedule.

    End on whichever comes first: headloss limit, turbidity breakthrough, or maximum run time. Time alone risks breakthrough.

    Filtration

  23. Adding more coagulant always improves settled turbidity.

    Overdosing re-stabilises the particles and turbidity gets worse. The jar test exists to find the turning point.

    Coagulation

  24. Lockout tagout is there to protect the equipment.

    It protects people from stored energy. Equipment protection is incidental and never the exam answer.

    Plant Safety

  25. If the water leaving the plant was safe, records are a formality.

    Records are the legal evidence of compliance. A gap in them is itself a violation, whatever the water quality was.

    Monitoring and Reporting