Symptom to First Move
Standard field troubleshooting practice
Worked in the order that costs the least. A leaking number one shut-off imitates almost every component failure on this list.
| Symptom | Check first |
|---|---|
| Relief valve discharges continuously | Whether it stops when downstream demand stops |
| Relief valve drips intermittently | Whether a heater or check valve was fitted recently |
| Relief valve will not open | The number 1 shut-off for leakage |
| Check reads low but holds | Reset the gauge and read again |
| Gauge falls straight to zero | Hose positions and needle valves |
| Needle bounces | Air in the hoses and flow through the assembly |
| Downstream will not reach atmosphere | The number 2 shut-off and any second feed |
| Air inlet never opens | The number 1 shut-off for leakage |
| PVB spits in service | The height above the highest outlet |
| Readings drift between attempts | Whether the gauge moved |
Check the figures against the edition of the Field Test Procedures your exam uses; local amendments can change them.