Symptom to First Move

Standard field troubleshooting practice

Worked in the order that costs the least. A leaking number one shut-off imitates almost every component failure on this list.

SymptomCheck first
Relief valve discharges continuouslyWhether it stops when downstream demand stops
Relief valve drips intermittentlyWhether a heater or check valve was fitted recently
Relief valve will not openThe number 1 shut-off for leakage
Check reads low but holdsReset the gauge and read again
Gauge falls straight to zeroHose positions and needle valves
Needle bouncesAir in the hoses and flow through the assembly
Downstream will not reach atmosphereThe number 2 shut-off and any second feed
Air inlet never opensThe number 1 shut-off for leakage
PVB spits in serviceThe height above the highest outlet
Readings drift between attemptsWhether the gauge moved

Check the figures against the edition of the Field Test Procedures your exam uses; local amendments can change them.