Power Line Clearance, Table A
29 CFR 1926.1408 Table A
Minimum clearance while operating near an energised line. The distance applies to any part of the equipment, the load line, or the load including rigging and lifting accessories. A line is assumed energised until the utility confirms it has been deenergised and visibly grounded at the worksite.
| Nominal voltage (kV, AC) | Minimum clearance |
|---|---|
| Up to 50 | 10 ft |
| Over 50 to 200 | 15 ft |
| Over 200 to 350 | 20 ft |
| Over 350 to 500 | 25 ft |
| Over 500 to 750 | 35 ft |
| Over 750 to 1,000 | 45 ft |
| Over 1,000 | Set by the utility owner or a registered PE |
Check the figures against the edition of the Load Chart & Operator Manual your exam uses; local amendments can change them.