Filtration Systems

Sand, precoat and cartridge, and what each one can pass.

Three filter types, and the exam expects you to know what separates them.

Sand is the workhorse. It passes the most water per square foot and gives the coarsest filtration, and it is the only one that improves slightly as it dirties, because the trapped material narrows the paths through the bed.

Precoat, usually diatomaceous earth, gives the finest filtration and passes the least water per square foot of the two pressure types. Cartridge is the smallest rate of all, which is why a cartridge plant is physically large for the flow it carries.

The number to remember is the ratio rather than the individual figures. Sand is allowed roughly fifty times the rate of cartridge, so a plant converted from one to the other without resizing is out of compliance from the first day.

Backwashing is driven by the pressure differential, not by the calendar.

Loading rate is gallons per minute per square foot of filter area. Filter area is the effective media area from the data plate, not the tank. Differential pressure is influent pressure minus effluent pressure. Precoat is the layer of media applied to the elements before filtering. Channelling is water finding a path through a sand bed rather than filtering evenly through it.

Loading rate questions give you a flow and an area and want a rate, or give you an area and a limit and want the most flow allowed. Both are one division.

If a question mentions a filter area, use it. The tank diameter is a distractor.