Skip to content

Filtration & Backwash

The backwash pumping rate, the water a wash uses as a share of the run's production, the unit filter run volume and the bed's rise rate.

Backwash pumping rate

6,000 gpm

Backwash 2.50% | UFRV 6,000 gal/sq ft

Backwash under 5% of production, which is the usual target.

How it's worked out

Backwash rate = area x rate, Backwash % = wash water / filtered

  1. Backwash pumping rate400.0 sq ft x 15.0 gpm/sq ft= 6,000 gpm
  2. Water used in the wash6,000 gpm x 10.0 min= 60,000 gallons
  3. Backwash percentage of water produced60,000 gal / 2,400,000 gal x 100= 2.50%
  4. Unit filter run volume2,400,000 gal / 400.0 sq ft= 6,000 gal/sq ft
  5. Backwash rise rate(15.0 gpm/sq ft x 12 in/ft) / 7.48= 24.06 in/min

The other thirteen tools