Tools
Filtration & Backwash
The backwash pumping rate, the water a wash uses as a share of the run's production, the unit filter run volume and the bed's rise rate.
Backwash pumping rate
6,000 gpm
Backwash 2.50% | UFRV 6,000 gal/sq ft
Backwash under 5% of production, which is the usual target.
How it's worked out
Backwash rate = area x rate, Backwash % = wash water / filtered
- Backwash pumping rate400.0 sq ft x 15.0 gpm/sq ft= 6,000 gpm
- Water used in the wash6,000 gpm x 10.0 min= 60,000 gallons
- Backwash percentage of water produced60,000 gal / 2,400,000 gal x 100= 2.50%
- Unit filter run volume2,400,000 gal / 400.0 sq ft= 6,000 gal/sq ft
- Backwash rise rate(15.0 gpm/sq ft x 12 in/ft) / 7.48= 24.06 in/min