Charging and Diagnosis Targets

Common manufacturer practice

Typical field values. The equipment data plate is always the authority for a specific unit.

MeasurementTypical targetWhat it means
Superheat, TXV, at the coil8 to 14 FThe valve holds this itself
Superheat, at the condensing unit10 to 30 FIncludes suction line heat pickup
Superheat, fixed orificeCalculated target(3 x indoor WB - 80 - outdoor DB) / 2
Subcooling8 to 12 FCharges a TXV system
Airflow350 to 450 cfm per tonBelow 350 the coil can freeze
Total external staticAt or under the blower ratingOften 0.5 in wg
Compression ratio, air conditioning2 to 4 to 1Above 10 is a problem
Capacitor tolerancePlus or minus 6%uF = 2652 x amps / volts
Voltage imbalanceUnder 2%Many makers' limit; NEMA derates above 1%

Check the figures against the edition of the EPA 608 Study Guide your exam uses; local amendments can change them.