Reading Superheat and Subcooling Together

Standard refrigeration diagnosis

Neither number diagnoses anything alone. This is the whole reason both are measured on the same visit.

SuperheatSubcoolingMost likely cause
HighLowUndercharge, so find the leak
HighHighRestriction between condenser and coil
LowHighOvercharge, so recover down
LowLowCompressor not pumping, or valve overfeeding
NormalNormalCharge is right, so confirm against the data plate