The 12 Section 608 tables that come up most on the exam. Each one is laid out in full, with the section it comes from.

  1. 01Required Levels of EvacuationBefore an appliance is opened it must be evacuated to this level. Which row applies depends on the refrigerant's pressure class, the charge size and when the appliance was made.40 CFR 82.156, Table 16 rows
  2. 02Appliance Pressure ClassesThe classes are defined by liquid saturation pressure at 104 F, not by boiling point. The class sets both the required evacuation level and the certification type needed to work on it.40 CFR 82.1524 rows
  3. 03Small Appliance RecoveryA small appliance is fully manufactured, charged and hermetically sealed in a factory with five pounds of refrigerant or less. Meeting any one of these satisfies the requirement.40 CFR 82.156 and 82.1524 rows
  4. 04Leak Rate TriggersApplies to appliances containing 50 pounds or more. Exceeding the trigger starts the repair clock.40 CFR 82.1576 rows
  5. 05Section 608 Certification TypesCertification is by appliance category and does not expire. Universal is awarded for passing all three type sections plus Core.40 CFR 82.1615 rows
  6. 06Dates That Appear on the ExamThe regulatory timeline, from the Montreal Protocol to the A2L transition.Clean Air Act s.608, AIM Act 202010 rows
  7. 07ASHRAE 34 Safety ClassificationThe letter is toxicity and the number is flammability. The L suffix marks a burning velocity of 10 cm/s or less, which is what makes an A2L usable in an occupied building.ASHRAE Standard 34 classification scheme6 rows
  8. 08Charging and Diagnosis TargetsTypical field values. The equipment data plate is always the authority for a specific unit.Common manufacturer practice9 rows
  9. 09Reading Superheat and Subcooling TogetherNeither number diagnoses anything alone. This is the whole reason both are measured on the same visit.Standard refrigeration diagnosis5 rows
  10. 10Constants and FormulasThe numbers that appear in field calculations, and where each one comes from.Standard engineering values9 rows
  11. 11Refrigerant and Oil CompatibilityPutting the wrong oil in a system starves the compressor, because the oil separates instead of circulating back with the refrigerant.Manufacturer practice5 rows
  12. 12Evacuation and Vacuum ReferenceA compound gauge cannot resolve any of this. Below atmospheric, a micron gauge is the only instrument that reads the useful range.Standard service practice8 rows