Code tables · 11 of 12
Refrigerant and Oil Compatibility
Manufacturer practice
Putting the wrong oil in a system starves the compressor, because the oil separates instead of circulating back with the refrigerant.
| Refrigerant family | Oil | Note |
|---|---|---|
| CFC and HCFC (R-12, R-22) | Mineral oil, alkylbenzene | Returns with the refrigerant |
| HFC (R-134a, R-404A, R-410A) | POE | Absorbs moisture within minutes of opening |
| HFO and A2L blends (R-454B, R-32) | POE | Same handling care as any HFC system |
| Ammonia (R-717) | Mineral oil | Oil does not mix; it is drained from the vessel |
| CO2 (R-744) | POE or PAG | Very high pressures throughout |
Check the figures against the edition of the EPA 608 Study Guide your exam uses; local amendments can change them.