Code tables · 10 of 12
Constants and Formulas
Standard engineering values
The numbers that appear in field calculations, and where each one comes from.
| Constant | Value | Used for |
|---|---|---|
| Sensible heat factor | 1.08 | Btu/h = 1.08 x cfm x dT, at sea level |
| Latent heat factor | 0.68 | Btu/h = 0.68 x cfm x grains difference |
| Total heat factor | 4.5 | Btu/h = 4.5 x cfm x enthalpy difference |
| Capacitance at 60 Hz | 2652 | uF = 2652 x amps / volts |
| One ton of refrigeration | 12,000 Btu/h | Melting one ton of ice in 24 hours |
| Standard atmosphere | 14.696 psi | Added to psig to get psia |
| Natural gas heating value | ~1,030 Btu/cu ft | Local utility publishes the exact figure |
| Round duct friction | 0.109136 x Q^1.9 / D^5.02 | in wg per 100 ft, galvanised |
| Rectangular equivalent | 1.30 x (ab)^0.625 / (a+b)^0.25 | Equivalent round diameter |
Check the figures against the edition of the EPA 608 Study Guide your exam uses; local amendments can change them.