Skip to content

Evacuation and Vacuum Reference

Standard service practice

A compound gauge cannot resolve any of this. Below atmospheric, a micron gauge is the only instrument that reads the useful range.

LevelEquivalentMeaning
760,000 microns0 in HgAtmospheric pressure
25,400 microns29 in HgAbout as far as a compound gauge reads
5,000 microns-Water still boiling at room temperature
1,000 microns-Acceptable on some service work
500 microns-Common target before charging
Rises then levels off-Moisture still boiling off
Rises steadily, never levels-A leak
25 mm Hg absolute25,000 micronsLow pressure appliance requirement

Check the figures against the edition of the EPA 608 Study Guide your exam uses; local amendments can change them.