Skip to content

Leak Rate Triggers

40 CFR 82.157

Applies to appliances containing 50 pounds or more. Exceeding the trigger starts the repair clock.

Appliance typeTriggerExample
Comfort cooling10% per yearOffice rooftop unit, chiller
Commercial refrigeration20% per yearSupermarket rack
Industrial process refrigeration30% per yearChemical plant
Repair deadline once triggered30 daysFrom date of discovery
Retrofit or retirement plan, if not repaired30 days to planOne year to complete
Charge that brings a system under the rules50 lb, ozone-depleting refrigerants; 15 lb, HFCs with a GWP above 53 (since 1 Jan 2026)40 CFR 82.157 and 84.106

Check the figures against the edition of the EPA 608 Study Guide your exam uses; local amendments can change them.