Code tables · 4 of 12
Leak Rate Triggers
40 CFR 82.157
Applies to appliances containing 50 pounds or more. Exceeding the trigger starts the repair clock.
| Appliance type | Trigger | Example |
|---|---|---|
| Comfort cooling | 10% per year | Office rooftop unit, chiller |
| Commercial refrigeration | 20% per year | Supermarket rack |
| Industrial process refrigeration | 30% per year | Chemical plant |
| Repair deadline once triggered | 30 days | From date of discovery |
| Retrofit or retirement plan, if not repaired | 30 days to plan | One year to complete |
| Charge that brings a system under the rules | 50 lb, ozone-depleting refrigerants; 15 lb, HFCs with a GWP above 53 (since 1 Jan 2026) | 40 CFR 82.157 and 84.106 |
Check the figures against the edition of the EPA 608 Study Guide your exam uses; local amendments can change them.