Required Levels of Evacuation

40 CFR 82.156, Table 1

Before an appliance is opened it must be evacuated to this level. Which row applies depends on the refrigerant's pressure class, the charge size and when the appliance was made.

Appliance typeMade before 15 Nov 1993Made on/after
Very high pressure0 in Hg0 in Hg
High pressure, under 200 lb0 in Hg0 in Hg
High pressure, 200 lb or more4 in Hg10 in Hg
Medium pressure, under 200 lb4 in Hg10 in Hg
Medium pressure, 200 lb or more4 in Hg15 in Hg
Low pressure25 mm Hg absolute25 mm Hg absolute

Check the figures against the edition of the EPA 608 Study Guide your exam uses; local amendments can change them.