Topic 05 · Core: Safety, Cylinders & Disposal
Core: Safety, Cylinders & Disposal
The safety material is where the exam stops being about paperwork. Most of it comes down to two hazards that have nothing to do with the ozone layer: refrigerant displaces oxygen, and refrigerant on a hot surface produces something far worse than refrigerant.
Where it lives. ASHRAE 15 for machinery rooms, DOT for cylinders in transport, OSHA for worker protection, and 40 CFR 82 for disposal.
What it covers. Asphyxiation and frostbite, decomposition products, machinery room monitors and ventilation, cylinder handling and the 125 degree limit, oil types and moisture, and the disposal chain.
On the exam. Questions usually describe a practice and ask whether it is acceptable. Heating a cylinder with a torch, using oxygen to pressure test and refilling a disposable cylinder are all deliberately offered as plausible.
A2L, A3 and B2L refrigerants are flammable to differing degrees. Mineral oil suits CFCs and HCFCs; POE suits HFCs and absorbs moisture from the air within minutes of the container being opened.
- Nitrogen, never oxygen or air. Oxygen with refrigerant oil under pressure can detonate.
- Three agencies, three jobs. EPA the refrigerant, DOT the cylinder in transit, OSHA the worker.
- Recover before opening, always. The reason for opening the system is irrelevant.