Topic 04 · Hazard & Assembly Selection
Hazard & Assembly Selection
Choosing the assembly. Two questions decide it, and the second one is the one candidates skip.
Question one: how bad is the substance if it comes back. Question two: can anything downstream ever make its own pressure.
High hazard with backpressure leaves exactly one answer, the reduced pressure principle assembly. High hazard with backsiphonage only also permits a vacuum breaker. Low hazard with backpressure permits a double check. Low hazard with backsiphonage only is the least demanding case on the list.
A higher rated assembly may always replace a lower one. Going the other way never works, whatever the size or the budget.
Health hazard: could cause illness or death.
Non-health hazard: objectionable but not dangerous.
Backpressure: downstream pressure exceeding the supply.
Backsiphonage: supply pressure falling below the downstream side.
Irrigation is a health hazard. That single fact catches more candidates than any other on the exam, and the reason is what is in the soil rather than what goes into the pipe.
Watch for the second half of a scenario. The same sprinkler system is a double check with plain water and an RP the moment antifreeze or foam appears. The building has not changed, only the substance.