Tools
Filter Rate
Gallons per minute per square foot of filter area, against the MAHC limit for sand, precoat or cartridge, and the most flow the filter may pass.
Loading rate
12.00 gpm/sq ft
80 percent of the 15.0 limit
Inside the limit. Loading rate is measured against the filter data plate area, not the tank size, and a filter with channelled or worn media does not achieve its rated area no matter what the plate says.
How it's worked out
Loading rate = flow / filter area
- Loading rate480.0 gpm / 40.0 sq ft= 12.00 gpm/sq ft
- Most this filter may pass15.0 x 40.0 sq ft= 600 gpm
- Limit for this filter typeMAHC 4.7.2.2.3.1= 15.0 gpm/sq ft