Gallons per minute per square foot of filter area, against the MAHC limit for sand, precoat or cartridge, and the most flow the filter may pass.

From the filter data plate, not the tank diameter

Loading rate

12.00 gpm/sq ft

80 percent of the 15.0 limit

Inside the limit. Loading rate is measured against the filter data plate area, not the tank size, and a filter with channelled or worn media does not achieve its rated area no matter what the plate says.

How it's worked out

Loading rate = flow / filter area

  1. Loading rate480.0 gpm / 40.0 sq ft= 12.00 gpm/sq ft
  2. Most this filter may pass15.0 x 40.0 sq ft= 600 gpm
  3. Limit for this filter typeMAHC 4.7.2.2.3.1= 15.0 gpm/sq ft