Topic 09 · Refrigerants, Blends & Oils
Refrigerants, Blends & Oils
This topic is where the numbering system, the blends and the oils come together. The single most useful idea is glide: whether a refrigerant has one saturation curve or two changes how it is charged, how it is diagnosed and what happens when it leaks.
Where it lives. ASHRAE Standard 34 for numbering and safety classes, AHRI 700 for purity, and manufacturer literature for oil compatibility.
What it covers. Azeotropes and zeotropes, the 400, 500, 600 and 700 series, glide and fractionation, latent and sensible heat, critical temperature, oil compatibility, retrofits, and the SNAP programme.
On the exam. Retrofit questions are common and the answer is rarely "just change the refrigerant". The oil is almost always the constraint.
A zeotrope boils across a range of temperatures at constant pressure; an azeotrope behaves like a pure fluid. The 400 series is zeotropic, the 500 series azeotropic.
- The series number tells you the behaviour. 400 glides, 500 does not, 600 is hydrocarbons, 700 is inorganics numbered by molecular weight.
- Charge a blend as liquid. Vapour withdrawal fractionates it.
- Mineral oil will not return with an HFC. It logs in the evaporator and the compressor runs dry.