Allowable ampacity of insulated conductors rated up to 2000 V, not more than three current-carrying conductors in a raceway, in an ambient of 30 °C. Anything outside that needs derating, and the termination rating on the gear can cap you at the 60 °C or 75 °C column no matter what the wire is rated for.

Copper

NEC Table 310.16

Size60 °C75 °C90 °C
14152025
12202530
10303540
8405055
6556575
4708595
385100115
295115130
1110130145
1/0125150170
2/0145175195
3/0165200225
4/0195230260
250 kcmil215255290
300 kcmil240285320
350 kcmil260310350
400 kcmil280335380
500 kcmil320380430

Amps. TW at 60 °C; THW and THWN at 75 °C; THHN and XHHW-2 at 90 °C.

Aluminium

NEC Table 310.16

Size60 °C75 °C90 °C
12152025
10253035
8354045
6405055
4556575
3657585
27590100
185100115
1/0100120135
2/0115135150
3/0130155175
4/0150180205
250 kcmil170205230
300 kcmil195230260
350 kcmil210250280
400 kcmil225270305
500 kcmil260310350

Amps. The table has no aluminium 14 AWG.

Before you use a number off this table

NEC 110.14(C), 310.15

  • The termination rating usually decides the column, not the wire. Most gear 100 A and below is listed for 60 °C.
  • Four or more current-carrying conductors in one raceway means adjustment — 80% at 4 to 6, 70% at 7 to 9.
  • An ambient above 30 °C means correction on top of that.
  • The neutral of a three-phase, four-wire circuit feeding non-linear load counts as current-carrying.