Ampacity
Allowable ampacity of insulated conductors rated up to 2000 V, not more than three current-carrying conductors in a raceway, in an ambient of 30 °C. Anything outside that needs derating, and the termination rating on the gear can cap you at the 60 °C or 75 °C column no matter what the wire is rated for.
Copper
NEC Table 310.16
| Size | 60 °C | 75 °C | 90 °C |
|---|---|---|---|
| 14 | 15 | 20 | 25 |
| 12 | 20 | 25 | 30 |
| 10 | 30 | 35 | 40 |
| 8 | 40 | 50 | 55 |
| 6 | 55 | 65 | 75 |
| 4 | 70 | 85 | 95 |
| 3 | 85 | 100 | 115 |
| 2 | 95 | 115 | 130 |
| 1 | 110 | 130 | 145 |
| 1/0 | 125 | 150 | 170 |
| 2/0 | 145 | 175 | 195 |
| 3/0 | 165 | 200 | 225 |
| 4/0 | 195 | 230 | 260 |
| 250 kcmil | 215 | 255 | 290 |
| 300 kcmil | 240 | 285 | 320 |
| 350 kcmil | 260 | 310 | 350 |
| 400 kcmil | 280 | 335 | 380 |
| 500 kcmil | 320 | 380 | 430 |
Amps. TW at 60 °C; THW and THWN at 75 °C; THHN and XHHW-2 at 90 °C.
Aluminium
NEC Table 310.16
| Size | 60 °C | 75 °C | 90 °C |
|---|---|---|---|
| 12 | 15 | 20 | 25 |
| 10 | 25 | 30 | 35 |
| 8 | 35 | 40 | 45 |
| 6 | 40 | 50 | 55 |
| 4 | 55 | 65 | 75 |
| 3 | 65 | 75 | 85 |
| 2 | 75 | 90 | 100 |
| 1 | 85 | 100 | 115 |
| 1/0 | 100 | 120 | 135 |
| 2/0 | 115 | 135 | 150 |
| 3/0 | 130 | 155 | 175 |
| 4/0 | 150 | 180 | 205 |
| 250 kcmil | 170 | 205 | 230 |
| 300 kcmil | 195 | 230 | 260 |
| 350 kcmil | 210 | 250 | 280 |
| 400 kcmil | 225 | 270 | 305 |
| 500 kcmil | 260 | 310 | 350 |
Amps. The table has no aluminium 14 AWG.
Before you use a number off this table
NEC 110.14(C), 310.15
- The termination rating usually decides the column, not the wire. Most gear 100 A and below is listed for 60 °C.
- Four or more current-carrying conductors in one raceway means adjustment — 80% at 4 to 6, 70% at 7 to 9.
- An ambient above 30 °C means correction on top of that.
- The neutral of a three-phase, four-wire circuit feeding non-linear load counts as current-carrying.