Voltage Drop

How many volts a run loses, as a share of the system voltage, and what reaches the load. Length is one way: the formula doubles it for you on single phase. The 3% and 5% are what the NEC advises, not what it requires.

Panel to load
Material
Phase
System voltage

Voltage drop

2.47 % drop

2.96 V lost · 117.0 V at the load

Inside the 3% the NEC advises for a branch circuit.

How it's worked out

VD = (2 or √3) × K × I × D ÷ CM

  1. Single phase counts the run twice — out and back2= × 2.000
  2. Copper at 12 is 6,530 circular mils2.000 × 12.9 × 15.0 × 50 ÷ 6,530= 2.96 V
  3. As a share of the system voltage2.96 ÷ 120 × 100= 2.47 %
  4. What arrives at the load120 − 2.96= 117.0 V