Skip to content

Torque Specs

A loose termination is the single most common cause of a burned lug. These are typical figures to get you close when the label is missing or unreadable — where the equipment gives a value, that value is the one the code requires.

Typical termination torque

NEC 110.14(D)

Sizein-lbft-lb
14252.1
12252.1
10252.1
8352.9
6453.8
4605.0
3605.0
2756.3
1756.3
1/0756.3
2/01008.3
3/01008.3
4/01008.3
250 kcmil15012.5
300 kcmil20016.7
350 kcmil20016.7
400 kcmil25020.8
500 kcmil25020.8

Typical values only. Always torque to the figure printed on the device or in its instructions.

Doing it properly

NEC 110.14(D)

  • A calibrated tool is required where the manufacturer gives a torque value. "Good and tight" is not a specification.
  • Torque once, to the figure. Re-torquing an already tight connection can loosen it.
  • Aluminium: use an antioxidant compound where the connector's instructions call for it.
  • Check the torque again after any fault or overheating event.

The other eleven tools