Tools
Torque Specs
A loose termination is the single most common cause of a burned lug. These are typical figures to get you close when the label is missing or unreadable — where the equipment gives a value, that value is the one the code requires.
Typical termination torque
NEC 110.14(D)
| Size | in-lb | ft-lb |
|---|---|---|
| 14 | 25 | 2.1 |
| 12 | 25 | 2.1 |
| 10 | 25 | 2.1 |
| 8 | 35 | 2.9 |
| 6 | 45 | 3.8 |
| 4 | 60 | 5.0 |
| 3 | 60 | 5.0 |
| 2 | 75 | 6.3 |
| 1 | 75 | 6.3 |
| 1/0 | 75 | 6.3 |
| 2/0 | 100 | 8.3 |
| 3/0 | 100 | 8.3 |
| 4/0 | 100 | 8.3 |
| 250 kcmil | 150 | 12.5 |
| 300 kcmil | 200 | 16.7 |
| 350 kcmil | 200 | 16.7 |
| 400 kcmil | 250 | 20.8 |
| 500 kcmil | 250 | 20.8 |
Typical values only. Always torque to the figure printed on the device or in its instructions.
Doing it properly
NEC 110.14(D)
- A calibrated tool is required where the manufacturer gives a torque value. "Good and tight" is not a specification.
- Torque once, to the figure. Re-torquing an already tight connection can loosen it.
- Aluminium: use an antioxidant compound where the connector's instructions call for it.
- Check the torque again after any fault or overheating event.