Full-load amps from NEC Table 430.248 or 430.250, then the conductor size at 125% and the inverse-time breaker at 250%. The code makes you size from the table value, not the nameplate.

Phase
Voltage

Full-load amps

7.6 A full load

Conductors 9.5 A · breaker up to 20 A

Size the conductors for at least 9.5 A and set the inverse-time breaker at 15 A. Because 250% falls between standard sizes, 430.52(C)(1) Exception No. 1 also allows the next size up, 20 A; if the motor still will not start, Exception No. 2 allows more. Use the table value, not the nameplate amps — the code requires it.

How it's worked out

FLA from NEC Table 430.250; conductors 125%; breaker 250%

  1. 5 hp, 460 V, Three phase — NEC Table 430.250table lookup= 7.6 A
  2. Conductors carry 125% of full load — NEC 430.227.6 × 1.25= 9.5 A
  3. Inverse-time breaker, 250% ceiling — NEC 430.527.6 × 2.5= 19.0 A
  4. Largest standard rating at or under that — NEC 240.6(A)round down to a standard size= 15 A