Tools
Trickling Filter
Pounds of BOD per day per 1,000 cubic feet of media, with the recirculation ratio, and whether the filter is low rate, high rate or roughing.
Organic loading
25.0 lbs BOD/day/1,000 ft³
Recirculation ratio 1.00 to 1
Intermediate to high rate range. Carbon removal, little nitrification.
How it's worked out
Organic Loading = lbs BOD per day / (media volume in units of 1,000 ft³)
- Pounds of BOD applied per day1.00 MGD x 120.0 mg/L x 8.34= 1,001 lbs/day
- Express the media volume in thousands of cubic feet40,000 ft³ / 1,000= 40.00 units
- Divide the load by the media volume1,001 / 40.00= 25.0 lbs/day/1,000 ft³
- Recirculation ratio1.00 MGD / 1.00 MGD= 1.00 to 1