Quick reference

The key points of all 18 Cross-Connection Control topics on one page. Search for a word, open a topic, and jump to its full notes when you need more.

  1. 01Cross-Connection FundamentalsEverything in backflow comes back to three words: the cross-connection is the piping, backflow is the event, and backpressure or backsiphonage is the cause. Get those straight and the rest of the exam follows.

    A cross-connection is the plumbing arrangement. Backflow is the event. Backpressure and backsiphonage are the only two causes of that event, and every question about protection comes back to which of the two is possible.

    Backpressure means something downstream can push harder than the supply: a pump, a boiler, compressed air, or simply an elevated tank. Backsiphonage means the supply itself falls away, usually because of a main break or a heavy fire flow nearby.

    Degree of hazard is about consequence. A health hazard could make somebody ill or worse. A non-health hazard would be objectionable, nothing more. Neither has anything to do with pressure, pipe size or cost.

    Open the full study notes
  2. 02RP Field TestThe reduced pressure principle test is the one candidates fail on. Learn it as five phases rather than thirty steps, and the bleed order and the gauge reset stop feeling arbitrary.

    Five phases. Prepare, observe check one, record the relief valve, observe check two under backpressure, then record the numbers and return to service.

    Nobody forgets that a relief valve opens at 2.0 psid. What people forget is which bleed closes first: the high bleed, every time, and the low bleed last.

    Two things separate a good tester from a fast one. Opening the low control no more than a quarter turn, so the relief valve reading is honest. And resetting the gauge before the check valve one reading, so disc compression does not inflate it.

    Open the full study notes
  3. 03CaliforniaCalifornia now sets tester certification through the State Water Board's handbook, with a recognised programme from 1 July 2026 and an ANSI accredited body from 1 July 2027. Those dates are the part to know.

    The State Water Resources Control Board now sets the requirement through the Cross-Connection Control Policy Handbook. Before this, testing authority was decided purveyor by purveyor, which is why older guidance says California has no state rule.

    From 1 July 2026 the certificate must come from a programme the State Water Board recognises. From 1 July 2027 only bodies accredited by ANSI to ISO/IEC 17024 will count.

    ASSE 5110 was formally recognised in June 2025 as meeting section 3.4.1 of the handbook, valid until the 2027 deadline.

    Open the full study notes
  4. 04Hazard & Assembly SelectionTwo questions choose every assembly: how bad is the substance, and can anything downstream make its own pressure. Most wrong answers come from skipping the second one.

    Question one: how bad is the substance if it comes back. Question two: can anything downstream ever make its own pressure.

    High hazard with backpressure leaves exactly one answer, the reduced pressure principle assembly. High hazard with backsiphonage only also permits a vacuum breaker. Low hazard with backpressure permits a double check. Low hazard with backsiphonage only is the least demanding case on the list.

    A higher rated assembly may always replace a lower one. Going the other way never works, whatever the size or the budget.

    Open the full study notes
  5. 05RP ConstructionAn RP is two checks, a zone between them and a relief valve that opens when the zone loses its margin. Learn its three numbers with the part each one belongs to: 2.0, 5.0 and the 3.0 buffer.

    Two independent checks with a zone between them, and a relief valve whose only job is to keep that zone below the supply pressure. The relief valve does not sense the checks at all. It senses the margin, and it opens when the margin is lost.

    That is what makes an RP different. A double check that fails goes on looking exactly the same. An RP that fails puts water on the floor.

    Three numbers live in this assembly and they belong to different components. The relief valve opens at 2.0 psid or higher. Check valve one holds 5.0 psid or higher. The buffer between them is 3.0 psid or higher.

    Open the full study notes
  6. 06DC ConstructionThe double check has two independent checks with one criterion, 1.0 psid and drip tight. It has nothing to show when a check stops sealing, which is exactly why it stays on low hazards.

    Both checks carry the same 1.0 psid criterion and both must close drip tight. There is no relief valve and there is nothing to tell you when a check has stopped sealing, which is exactly why the assembly is not approved for a health hazard.

    It loses less pressure than an RP of the same size and it may be installed in a vault, because it has no relief port to be submerged. Those two facts are why fire services so often use one.

    The detector version adds a metered bypass. The meter only has to register movement, never to measure accurately.

    Open the full study notes
  7. 07PVB & SVB ConstructionThe PVB and the SVB each have one check and one air inlet, both at 1.0. Neither can resist backpressure, whatever the height, and the PVB must sit twelve inches above the highest outlet.

    Both assemblies carry the same two criteria, and both are 1.0. The air inlet must begin to open at 1.0 psi or higher above atmosphere and must open fully once the body drains. The check valve must hold 1.0 psid or higher.

    Neither protects against backpressure. That is not a limitation that can be designed around, and it is why a vacuum breaker on a boiler feed or a pumped line is simply wrong.

    A PVB must sit at least twelve inches above the highest downstream outlet. Below that there is no siphon for the air inlet to break.

    Open the full study notes
  8. 08Air Gaps & DevicesAn air gap beats every assembly because nothing in it can fail, but it breaks the pressure. Learn the twice-the-opening rule with its one inch floor, and the limits on devices that cannot be tested.

    An air gap is twice the effective opening, and never less than one inch. A near wall raises the multiple to three. It is measured from the lowest point of the outlet down to the flood level rim, not to the overflow, because an overflow can block.

    An atmospheric vacuum breaker may not be used under continuous pressure. The usual limit is twelve hours in any twenty four, and it must sit downstream of the last control valve and at least six inches above the outlets.

    A device cannot be field tested. That is what limits devices to lesser applications, not the number of barriers inside them.

    Open the full study notes
  9. 09DC Field TestThe double check test is one measurement taken twice, and the best procedure to learn first. Keep the gauge level with the reference, because a foot of error is 0.433 psi against a 1.0 criterion.

    Straddle the check with the gauge, isolate the assembly, bring the downstream side to atmosphere, and read the differential when the flow stops and the needle settles. Then move one cock downstream and do it again.

    The gauge centre line must be level with the downstream test cock reference. Every foot off level shifts the reading by 0.433 psi, and against a 1.0 psid criterion two feet of error is most of the available margin.

    A reading that falls away to zero is a leak, not a low number, and it is recorded that way.

    Open the full study notes
  10. 10PVB & SVB Field TestThe vacuum breaker tests are short, and the favourite question is their order: a PVB tests the air inlet first, an SVB tests its check first. Drop the pressure slowly or the reading comes out low.

    The canopy comes off first on both, because watching the poppet move is half the test.

    On a PVB the air inlet is tested first, from test cock two, with the kit held level with the air inlet. On an SVB the check valve is tested first, using the vent valve to bring the body to atmosphere without spilling.

    On both, the pressure is dropped slowly, no more than a quarter turn of the high bleed. Dropping it fast reads low, exactly as it does on an RP relief valve.

    Open the full study notes
  11. 11Gauges & CalibrationA differential gauge reads a difference, and its calibration date can quietly sink a year of reports. Keep it in date, purge the air out of the hoses and hold it level.

    A differential gauge reads the difference between its two sides. Neither individual pressure is what the criteria are written against.

    The calibration rule is the one that costs money. Most programmes require an accuracy check within the twelve months before the test, and the stricter ones require an independent laboratory rather than the person who owns the gauge. A report taken with an expired gauge can be rejected months after the work was done.

    Air left in a hose makes the needle drift, because air is compressible. Purging both sides is what makes a reading repeatable.

    Open the full study notes
  12. 12HydraulicsTwo numbers carry most of the hydraulics: one psi lifts water 2.31 feet, and one foot of water is 0.433 psi. Add atmospheric pressure, velocity and thermal expansion, and you have the whole topic.

    One psi supports 2.31 feet of water. One foot of water produces 0.433 psi. Those two figures cover every gauge elevation question and every residual pressure question on the exam.

    Atmospheric pressure at sea level is 14.7 psi, which supports about 34 feet of water. That is why a barometric loop is built around 35 feet, and why a vacuum reading implying more lift than that cannot be real.

    Fitting any assembly turns an open service into a closed one. Heated water then has nowhere to go and the heater relief valve becomes the pressure control, which it was never meant to be.

    Open the full study notes
  13. 13Installation & ClearancesBefore the gauge comes out, check the installation: the height above grade, the PVB and AVB heights above the outlets, a relief port that vents freely, and enough room to test.

    Twelve inches from grade to the bottom of the assembly is the usual minimum, and about thirty inches to the centre line is the usual maximum. A PVB must also sit twelve inches above the highest downstream outlet, and an atmospheric vacuum breaker six inches.

    An RP relief port discharges to atmosphere through an air gap. It is never directly connected to a drain, because that connection would become the cross-connection the assembly was fitted to eliminate.

    An assembly that cannot be reached cannot be tested, and an assembly that is not tested stops being protection the year after it goes in.

    Open the full study notes
  14. 14Troubleshooting & RepairMost faults that look like a failed part are something cheaper. Rule out the shut-offs and your own kit first, then work through the likely causes in the order that costs the least.

    One fault imitates almost every other. A leaking number one shut-off keeps feeding the assembly during the test, so nothing behaves as it should. Relief valves appear not to open. Air inlets appear not to move. Suspect it first, every time.

    A relief valve that discharges continuously may be a hydraulic problem rather than a component fault. If the discharge stops when a downstream valve closes, the supply cannot hold the margin at that flow and rebuilding the assembly will not help.

    A gauge that falls straight to zero has four common causes and three of them are the tester rather than the valve.

    Open the full study notes
  15. 15Regulations & ReportingThe assembly is tested every year and the tester's certificate usually runs three. Know who requires what, which standards cover people and which cover products, and where the report goes.

    The device is tested annually. The tester certificate normally runs three years. Those two intervals are different things and mixing them up is the most common administrative error in the trade.

    The ASSE 5000 series covers people: 5110 tester, 5120 cross-connection control surveyor, 5130 repairer, 5150 programme administrator. The 1000 series covers products: 1013, 1015, 1020 and 1056.

    Reports go to the water purveyor, which keeps the compliance record. Many purveyors accept only their own form.

    Open the full study notes
  16. 16TexasTexas licenses testers through the TCEQ: a three year BPAT licence with twenty four hours of continuing education across the term, and reports that go to the water purveyor.

    The Texas Commission on Environmental Quality issues the Backflow Prevention Assembly Tester licence. It runs three years and requires twenty four hours of continuing education across the term.

    The licence covers testing and repair on domestic, commercial, industrial and irrigation services. It does not automatically put a tester on a city list, and several cities run their own separate registration.

    Reports go to the water purveyor rather than to the TCEQ.

    Open the full study notes
  17. 17WashingtonWashington renews the tester certificate every year and has the strictest gauge rule: an independent laboratory check within the twelve months before every test.

    The Backflow Assembly Tester certificate renews annually, which is the exception to the three year rule that applies almost everywhere else. The renewal is a fee plus a professional growth requirement met by examination, not a full retest.

    The gauge rule is the tightest in the country. The kit must be evaluated for performance, pressure tested and checked for accuracy within the twelve months before the test, by an independent laboratory. A shop check by the gauge owner does not satisfy it.

    Assemblies are tested annually, and the state rule names the USC manual directly.

    Open the full study notes
  18. 18OhioOhio certifies backflow technicians through the Department of Commerce in three classes that are not interchangeable, with a twenty four hour first course and a three year certificate.

    The Department of Commerce, Division of Industrial Compliance, certifies backflow technicians under Ohio Revised Code 3703.21. Ohio regulates isolation devices through the plumbing side, so containment at the service remains the purveyor's business.

    There are three classes. Class A covers isolation devices generally, Class B is limited to lawn irrigation, and Class C is for devices owned by a public water system. Holding B does not let you test a restaurant.

    The initial course is twenty four hours with a mandatory hands-on testing and repairing examination, and five years of relevant experience or an equivalent credential is expected.

    Open the full study notes