Quick reference

The key points of all 10 Section 608 topics on one page. Search for a word, open a topic, and jump to its full notes when you need more.

  1. 01Core: Ozone, Climate & RegulationThe Core section is mostly dates, definitions and thresholds: ozone and climate, the Montreal Protocol, ODP and GWP, when venting became illegal, what the AIM Act changed, certification types, penalties and records. You can't work any of it out, so it has to be learned.

    Where it lives. Section 608 of the Clean Air Act, implemented in 40 CFR Part 82 Subpart F. The AIM Act of 2020 sits alongside it and drives the HFC phase-down and the 2025 equipment transition.

    What it covers. Ozone chemistry, the Montreal Protocol, ODP and GWP, the venting prohibition and its dates, the sales restriction, certification types, penalties and record keeping.

    On the exam. Dates are asked directly, with the wrong answers being other real dates from the same timeline. Learn them as a sequence rather than as isolated facts, because the sequence is what makes them stick.

    Open the full study notes
  2. 02Core: Recovery, Recycling & ReclaimRecovery, recycling and reclaim sound the same and are three different things in law, and the exam tests the difference with scenarios. The deciding question is usually whether the refrigerant changed owner. Cylinders, the 80 percent fill limit and evacuation are here too.

    Where it lives. 40 CFR 82.152 for the definitions, 82.154 for the prohibitions and 82.158 for equipment standards.

    What it covers. The three R's, cylinder rules and the 80 percent fill limit, DOT approval and retest intervals, non-condensables, evacuation and vacuum measurement, and the difference between a recovery machine and a vacuum pump.

    On the exam. Expect scenarios rather than definitions: refrigerant is removed, cleaned somehow, and put somewhere. Work out where it ended up and who owns it, and the answer follows.

    Open the full study notes
  3. 03A2L Refrigerants & the 2025 TransitionA2L refrigerants are the biggest change to the trade in thirty years. Superheat, subcooling, evacuation and recovery all work as before; what's new is that the refrigerant can burn. Ignition sources, rated equipment, left-hand threads, leak sensors, charge limits and the 2025 transition.

    Where it lives. The AIM Act of 2020 and its Technology Transitions Rule, with equipment requirements in UL and IEC 60335-2-40 and classification in ASHRAE Standard 34.

    What it covers. The A2L classification, the 2025 transition, R-454B, R-32 and R-452B, cylinder markings and left-hand threads, rated recovery equipment, leak sensors and mitigation, charge limits, and blend glide.

    On the exam. Section 608 itself has not changed for A2L, and questions often test exactly that: existing certification stays valid. Employer and manufacturer training is a separate requirement.

    Open the full study notes
  4. 04Core: Leak Repair & RecordsThree leak rates, one repair deadline and one charge threshold carry most of the marks. Comfort cooling is the tightest rate and industrial process the loosest, and the exam expects you to work a leak out as a yearly rate from the refrigerant added.

    Where it lives. 40 CFR 82.157, with record keeping in 82.166.

    What it covers. The 50 pound threshold, the three trigger rates, the 30 day repair deadline, verification testing, retrofit and retirement plans, and the leak detection methods and their limitations.

    On the exam. Calculation questions give a charge size and a quantity added over a period, and expect the rate to be annualised. Adding 12 pounds to a 100 pound system over three months is 48 percent per year, not 12.

    Open the full study notes
  5. 05Core: Safety, Cylinders & DisposalWhere the exam stops being about paperwork. Refrigerant pushes out the oxygen you breathe, and refrigerant on a hot surface makes something far worse. Machinery room monitors, cylinder handling and the 125 degree limit, oils, moisture and disposal.

    Where it lives. ASHRAE 15 for machinery rooms, DOT for cylinders in transport, OSHA for worker protection, and 40 CFR 82 for disposal.

    What it covers. Asphyxiation and frostbite, decomposition products, machinery room monitors and ventilation, cylinder handling and the 125 degree limit, oil types and moisture, and the disposal chain.

    On the exam. Questions usually describe a practice and ask whether it is acceptable. Heating a cylinder with a torch, using oxygen to pressure test and refilling a disposable cylinder are all deliberately offered as plausible.

    Open the full study notes
  6. 06Type I: Small AppliancesType I is the smallest section, with the most specific numbers: the five pound factory-sealed definition, the 80 and 90 percent recovery requirements, the 4 inch vacuum alternative, and passive versus self-contained recovery. Whether the compressor works changes the answer.

    Where it lives. 40 CFR 82.156 for the recovery requirements and 82.152 for the definition.

    What it covers. The five pound factory sealed definition, the 80 and 90 percent recovery requirements, the 4 inch vacuum alternative, passive versus self-contained recovery, piercing valves, and charging small sealed systems by weight.

    On the exam. The compressor is the variable that changes the answer. A working compressor helps push the charge out, so the requirement rises to 90 percent; without one it stays at 80.

    Open the full study notes
  7. 07Type II: High Pressure AppliancesType II covers the equipment most technicians work on: the pressure classes, the evacuation table, liquid and push-pull recovery, TXV and fixed-orifice charging, and reading superheat and subcooling together. Learn the evacuation table as a pattern, not cell by cell.

    Where it lives. 40 CFR 82.156 Table 1 for evacuation levels and 82.152 for the pressure class definitions.

    What it covers. The pressure classes, required evacuation levels, liquid and push-pull recovery, non-condensables, TXV and fixed orifice charging, superheat and subcooling, compression ratio, and system components.

    On the exam. Diagnosis questions give superheat and subcooling together and ask what is wrong. Learn the four combinations as a grid rather than as four separate facts.

    Open the full study notes
  8. 08Type III: Low Pressure ChillersEverything about Type III follows from one fact: a low-pressure chiller runs in a vacuum. That explains the purge unit, the freezing hazard during recovery, the deepest evacuation level in the tables and the very low test pressure.

    Where it lives. 40 CFR 82.156 for the 25 mm Hg absolute requirement, and 82.152 for the low pressure definition.

    What it covers. Vacuum operation and air ingress, purge units and their efficiency, the 32 degree freezing hazard during recovery, rupture discs and test pressures, centrifugal compressors and surge, approach temperature, and R-123 exposure limits.

    On the exam. Questions often describe a symptom, such as a purge running constantly or an approach temperature that has risen, and ask for the cause. Both point back to air getting in or heat transfer getting worse.

    Open the full study notes
  9. 09Refrigerants, Blends & OilsHow refrigerants are numbered and grouped, blends and their glide, and which oil goes with which refrigerant. Glide is the idea to hold on to: whether a refrigerant has one saturation curve or two changes how you charge it, diagnose it and deal with a leak.

    Where it lives. ASHRAE Standard 34 for numbering and safety classes, AHRI 700 for purity, and manufacturer literature for oil compatibility.

    What it covers. Azeotropes and zeotropes, the 400, 500, 600 and 700 series, glide and fractionation, latent and sensible heat, critical temperature, oil compatibility, retrofits, and the SNAP programme.

    On the exam. Retrofit questions are common and the answer is rarely "just change the refrigerant". The oil is almost always the constraint.

    Open the full study notes
  10. 10Service, Airflow & DiagnosisWhere the calculators earn their place: static pressure, airflow, delta-T, target superheat, capacitor tests, voltage imbalance, MCA and MOCP, gas input and temperature rise, the fan laws and duct sizing. Almost every question here maps onto a tool.

    Where it lives. Manufacturer service literature and standard engineering practice, with the electrical method following NEC 440.

    What it covers. Total external static pressure, airflow per ton, the target delta-T, wet bulb measurement, target superheat, capacitor testing, voltage imbalance, MCA and MOCP, gas furnace input and temperature rise, the fan laws and duct sizing.

    On the exam. Airflow is the answer far more often than charge. A wide temperature split, a high temperature rise and a high static pressure are all the same fault seen from three directions.

    Open the full study notes