Airflow from a sensible capacity and the temperature change across the coil, and cfm per ton, with the constant thinned for altitude.

12,000 Btu/h per ton
Thin air carries less heat per cubic foot

Airflow

855 cfm

427 cfm per ton

Cooling systems are designed around roughly 350 to 450 cfm per ton. Below that the coil can freeze; above it the system stops removing humidity even though the thermostat is satisfied.

How it's worked out

cfm = Btu/h / (1.08 x dT)

  1. Divide the sensible load by the constant times the split24,000 / (1.080 x 26.0)= 855 cfm