Charge Check

Superheat and subcooling together, for any of 22 refrigerants, with what the pair says about the charge. Superheat is read from the dew point and subcooling from the bubble point, which matters on every blend.

Metering device
Where the suction reading was taken

Superheat and subcooling

10.2 F superheat · 10.0 F subcooling

CHARGE LOOKS CORRECT

Superheat
10.2 F in its normal band
Subcooling
10.0 F a normal liquid seal

Superheat and subcooling are both in their normal bands and they agree with each other. Confirm against the figures on the data plate, which is the authority for this specific unit.

How it's worked out

SH = suction line temp - saturated vapour temp; SC = saturated liquid temp - liquid line temp

  1. Look the suction pressure up on the R-410A dew point curve118.0 psig= 39.8 F saturated vapour
  2. Subtract that from the measured line temperature50.0 F - 39.8 F= 10.2 F superheat
  3. Look the liquid pressure up on the R-410A bubble point curve342.0 psig= 105.0 F saturated liquid
  4. Subtract the measured liquid line temperature105.0 F - 95.0 F= 10.0 F subcooling