How much refrigerant a line set needs past the length the unit ships charged for, worked out from the copper's volume and the liquid's density.

Liquid line size
On the data plate

Charge to add

10.9 oz to add

0.68 lb, at 0.54 oz per foot

Weigh this in with a scale, not by gauge pressure. The figure assumes a nominal 0.030 in wall ACR tube and liquid at 95 F; where the manufacturer publishes a per-foot value for the exact model, that value wins.

How it's worked out

oz = line volume x liquid density

  1. Inside area of the liquid linepi x (0.315 in / 2)^2= 0.0779 sq in
  2. Weigh a foot of liquid R-410A at 95 F0.00054 sq ft x 62.7 lb/cu ft= 0.54 oz per foot
  3. Multiply by the length past the factory charge35 - 15 = 20 ft= 10.9 oz