Clock the Gas Meter

What a furnace is actually burning, from the time one turn of the meter dial takes, against its rated input.

The gas utility publishes the local figure

Measured input

103,000 Btu/h input

103.0% of the 100,000 Btu/h rating

Within the range a field measurement can resolve. High altitude installations are derated on purpose : check the installation instructions before calling that underfired.

How it's worked out

Input = (3600 / sec) x dial size x heating value

  1. Scale one revolution up to an hour3600 / 72.0 x 2.00 cu ft= 100.0 cu ft per hour
  2. Multiply by the heating value of the gas100.0 x 1,030 Btu= 103,000 Btu/h
  3. Compare against the data plate103,000 / 100,000= 103.0% of rated