Clock the Gas Meter
What a furnace is actually burning, from the time one turn of the meter dial takes, against its rated input.
Measured input
103,000 Btu/h input
103.0% of the 100,000 Btu/h rating
Within the range a field measurement can resolve. High altitude installations are derated on purpose : check the installation instructions before calling that underfired.
How it's worked out
Input = (3600 / sec) x dial size x heating value
- Scale one revolution up to an hour3600 / 72.0 x 2.00 cu ft= 100.0 cu ft per hour
- Multiply by the heating value of the gas100.0 x 1,030 Btu= 103,000 Btu/h
- Compare against the data plate103,000 / 100,000= 103.0% of rated