Minimum circuit ampacity and maximum overcurrent protection from the compressor and fan amps, to check the wire and breaker someone else installed.

Minimum circuit ampacity

18.8 A minimum circuit ampacity

25 A maximum overcurrent protection

These are the figures the data plate should already carry, and the plate wins where it differs. The point of working them out is to check that the breaker and conductor someone else installed actually match the equipment. Note the rounding is down, not up : a breaker larger than the calculated maximum does not protect the equipment.

How it's worked out

MCA = 1.25 x largest motor + others; MOCP = 1.75 x largest + others

  1. Take the compressor at 125%1.25 x 14.1 A= 17.63 A
  2. Add every other load at 100%17.63 + 1.20= 18.83 A
  3. Take the compressor at 175% for the breaker1.75 x 14.1 + 1.20= 25.88 A
  4. Round down to a breaker that exists25.88 A= 25 A