Voltage Imbalance
The imbalance across the three legs of a three phase supply, as a percentage of the average.
Imbalance
0.87% imbalance
average 230.0 V
A healthy supply. Take the readings at the load side of the contactor with the equipment running, not at rest.
How it's worked out
Imbalance = max deviation from average / average x 100
- Average the three legs(230.0 + 232.0 + 228.0) / 3= 230.0 V
- Find the leg furthest from the averagelargest |leg - 230.0|= 2.0 V
- Express that as a percentage2.0 / 230.0 x 100= 0.87%