What a change of blower speed does to airflow, static pressure and motor power. Power follows the cube of speed.

New airflow

1,111 cfm

0.62 in wg static

Power rises with the cube of speed, so a small increase in airflow is a large increase in load. Check the motor nameplate amps before speeding a blower up, not after.

How it's worked out

cfm ~ rpm, pressure ~ rpm^2, power ~ rpm^3

  1. Speed ratio1,000 / 900= 1.111
  2. Airflow follows the ratio1,000 x 1.111= 1,111 cfm
  3. Static pressure follows the square0.50 x 1.111^2= 0.62 in wg
  4. Power follows the cube0.50 x 1.111^3= 0.686 hp