Static Pressure
Total external static pressure from the supply and return readings, against the blower's rating.
Total external static
0.40 in wg total
supply 0.25 + return 0.15
Within the blower rating. Compare the two sides against each other as well, because a system can total correctly while one side does all the restricting.
How it's worked out
TESP = |supply static| + |return static|
- Take the size of each reading, ignoring the sign|0.25| + |-0.15|= 0.40 in wg
- Compare against the blower rating0.40 / 0.50= 80% of rated