Target Superheat

The superheat a fixed orifice system should be charged to today, from the return air wet bulb and the outdoor dry bulb. A TXV system is charged by subcooling instead.

Measured in the return, not the room
In the shade, away from the condenser discharge

Target superheat

12.0 F superheat

Charge until the measured superheat matches this. It moves with the weather, so it has to be recalculated on the day rather than carried over from the last visit. Fixed orifice systems only, since a TXV holds its own superheat and is charged by subcooling.

How it's worked out

Target SH = (3 x IWB - 80 - ODB) / 2

  1. Three times the indoor wet bulb3 x 63.0 F= 189.0 F
  2. Subtract 80 and the outdoor dry bulb189.0 - 80 - 85.0= 24.0
  3. Halve it24.0 / 2= 12.0 F