Delta-T

The temperature split the coil should give in the conditions you measured, and what it is actually doing. The target moves with humidity, and a wide split is a symptom, not a good sign.

Leave blank for the target alone

Actual split

18.0 F actual

target 20.0 F

Within 3 F of target, which is as close as field instruments justify.

How it's worked out

Target dT = 0.4 x RDB - RWB + 53

  1. Take four tenths of the return dry bulb0.4 x 75.0 F= 30.0
  2. Subtract the wet bulb and add the chart constant30.0 - 63.0 + 53= 20.0 F target split
  3. Measure what the coil is actually doing75.0 F - 57.0 F= 18.0 F actual split