Air Gap

The air gap an outlet needs: twice the effective opening, three times near a wall, and never less than one inch.

The inside diameter of the outlet, or of the relief port
Obstructions

Minimum air gap

1.50 in

Clear of obstructions

Measured vertically from the lowest point of the outlet down to the flood level rim. An air gap is the only method that cannot fail mechanically, which is why it outranks every assembly.

How it's worked out

Air gap = 2 x effective opening, never less than 1 in

  1. Apply the multiplier0.750 in x 2= 1.50 in
  2. Apply the one inch floorGreater of 1.50 and 1.00= 1.50 in