DC Pass or Fail

Whether a double check passed: each check at 1.0 psid or higher and both drip tight.

Check valve #1
Check valve #2

Result

PASSED

Return to service

Both checks hold. On a detector assembly, confirm the bypass meter registered flow before signing the report.

How it's worked out

CV1 >= 1.0 psid and CV2 >= 1.0 psid, both drip tight

  1. Check valve #1 differential2.4 against a 1.0 psid minimum= Pass
  2. Check valve #2 differential1.8 against a 1.0 psid minimum= Pass
  3. TightnessA gauge reading that falls to zero means a leak= Both closed tight