Tools
Troubleshooting
Eleven symptoms with their real causes in order. The most valuable line in here is that a leaking number 1 shut-off imitates almost every component failure.
Relief valve discharges continuously (RP)
- 1. Fouled first check, holding less than the relief valve needs
- 2. Debris or damage on the relief valve seat
- 3. Supply pressure fluctuating, so the zone keeps losing its margin
- 4. Backpressure from downstream getting past the second check
- 5. Downstream demand so high that the first check cannot keep a differential
- Before you condemn a part: Watch it under different flow conditions before opening it up. Continuous discharge that stops when a downstream valve closes is a hydraulic problem, not a component failure.
Relief valve drips now and then (RP)
- 1. Pressure fluctuation on the supply, common near a pump station
- 2. A small piece of debris intermittently on the first check seat
- 3. Thermal expansion downstream with nowhere to go
- Before you condemn a part: Ask whether a water heater was fitted or a check valve added recently. Thermal expansion in a newly closed system shows up as an intermittent relief discharge and the assembly is innocent.
Relief valve will not open at all during the test (RP)
- 1. The number 1 shut-off is passing water, so the pressure never falls
- 2. Sensing passage blocked
- 3. Relief valve stuck or seized
- Before you condemn a part: Suspect the shut-off first. Work it open and closed to reseat it and try again before you take the relief valve apart.
Check valve differential is low but the valve is not leaking (RP, DC)
- 1. Worn or swollen rubber on the disc
- 2. Weak or broken spring
- 3. Scale or debris holding the disc slightly off its seat
- 4. Disc compression not relieved before reading, giving a false high number earlier and a low one now
- Before you condemn a part: Reset the gauge on the low bleed and read it again. A number that changes after a reset was a compression artefact.
Gauge falls straight to zero (RP, DC)
- 1. The check being tested is leaking
- 2. Hoses on the wrong test cocks
- 3. A needle valve left open
- 4. Air never purged, so the column collapses
- Before you condemn a part: Check your own kit before you condemn the assembly. Three of those four causes are the tester, not the valve.
Needle bounces and will not settle (all four)
- 1. Air still in the hoses
- 2. Flow still moving through the assembly
- 3. A partly open needle valve
- Before you condemn a part: Purge both sides again, high then low, and confirm the downstream shut-off is properly closed.
Downstream side will not come down to atmosphere (RP, DC)
- 1. The number 2 shut-off is passing water back in
- 2. A bypass or a second service feeding the same downstream piping
- 3. A booster pump running downstream
- Before you condemn a part: Look for another way in before blaming the valve. A second feed into the same piping is common on older commercial buildings and it makes the assembly untestable until it is isolated.
Air inlet never opens as the pressure falls (PVB, SVB)
- 1. The number 1 shut-off is passing water and keeps feeding the body
- 2. Poppet fouled, corroded or stuck to its seat
- 3. Freeze damage
- Before you condemn a part: Work the number 1 shut-off open and closed and repeat. If it still will not open, crack test cock 1 to drop the pressure another way and see whether the inlet moves. An inlet that opens then was never the fault.
Assembly spits water out of the air inlet in normal service (PVB)
- 1. Air inlet fouled and not sealing
- 2. Pressure fluctuation on the supply
- 3. The assembly is fitted lower than the outlets it protects
- Before you condemn a part: Measure the height first. A PVB below the highest downstream outlet is both spitting and useless, and no amount of rebuilding will fix a wrong installation.
Water keeps running from the vent during the check valve test (SVB)
- 1. The number 1 shut-off is passing water
- Before you condemn a part: Open the bleed-off slowly until the vent is down to a drip, then take the reading. If it cannot be brought down to a drip, the shut-off needs repair or replacement before the assembly can be tested.
Readings drift between the first and second reading (all four)
- 1. The gauge moved between readings and picked up an elevation error
- 2. Temperature change in a hose sitting in the sun
- 3. The gauge is out of calibration
- Before you condemn a part: Every foot the gauge moves shifts the reading by 0.433 psi. On a 1.0 psid criterion that is most of the margin.
The other twenty-three tools
Paperwork
The test
- DC Test WalkthroughStep by step, at the assembly
- RP Test WalkthroughStep by step, at the assembly
- PVB Test WalkthroughStep by step, at the assembly
- SVB Test WalkthroughStep by step, at the assembly
- RP Pass or FailReadings judged against the rule
- DC Pass or FailReadings judged against the rule
- PVB / SVB Pass or FailReadings judged against the rule
- Gauge ElevationCorrecting for where it hangs