Tools
Applications
Thirteen real installations, each classified by its hazard, with the reason. Irrigation is a health hazard and most people get that wrong.
Applications and the minimum assembly
Each worked by the Which Assembly rule. This is the floor, never a permission: the authority having jurisdiction can require more and frequently does.
- Lawn irrigation, no pump, no chemical injection: high hazard, backsiphonage only, so at least PVB. Irrigation is a health hazard because of what is in the soil, not because of the water going in. That surprises people.
- Lawn irrigation with a fertiliser injector: high hazard, backpressure possible, so at least RP. The injector is a pressure source. The moment chemicals are pumped in, a vacuum breaker is no longer enough.
- Boiler feed with treatment chemicals: high hazard, backpressure possible, so at least RP. A boiler makes its own pressure and the treatment is toxic. This is the textbook RP.
- Fire sprinkler, wet pipe, no antifreeze, no booster: low hazard, backpressure possible, so at least DC. Stagnant water in black steel is objectionable rather than dangerous. Add antifreeze or a booster pump and it changes.
- Fire sprinkler with antifreeze or foam: high hazard, backpressure possible, so at least RP. The additive is the hazard. The same building, the same pipe, a different answer.
- Carbonated beverage dispenser: high hazard, backpressure possible, so at least RP. Carbon dioxide pressure pushes back, and carbonic acid leaches copper out of the tube. Copper piping is prohibited downstream.
- Commercial dishwasher or laundry: high hazard, backpressure possible, so at least RP. Detergents and pumped rinse water.
- Cooling tower with treatment: high hazard, backpressure possible, so at least RP. Treated recirculating water under pump pressure.
- Hose bibb on a residence: high hazard, backsiphonage only, so at least PVB. A hose left in a bucket or a drain is the classic backsiphonage path. A hose connection vacuum breaker handles it, and it is a device rather than a testable assembly.
- Food-grade process water, no chemicals, gravity fed: low hazard, backsiphonage only, so at least DC. Objectionable if it came back, not dangerous.
- Reclaimed or recycled water service: high hazard, backpressure possible, so at least RP. Purple pipe. Treated as a health hazard everywhere.
- Medical or dental equipment: high hazard, backpressure possible, so at least RP. Aspirators and process equipment can both contaminate and push.
- Elevated storage tank filled through the top, no pump: low hazard, backpressure possible, so at least DC. The stored column itself is the pressure source. Elevation counts as backpressure even with no pump on site.
The other twenty-three tools
Paperwork
The test
- DC Test WalkthroughStep by step, at the assembly
- RP Test WalkthroughStep by step, at the assembly
- PVB Test WalkthroughStep by step, at the assembly
- SVB Test WalkthroughStep by step, at the assembly
- RP Pass or FailReadings judged against the rule
- DC Pass or FailReadings judged against the rule
- PVB / SVB Pass or FailReadings judged against the rule
- Gauge ElevationCorrecting for where it hangs