Thirteen real installations, each classified by its hazard, with the reason. Irrigation is a health hazard and most people get that wrong.

Applications and the minimum assembly

Each worked by the Which Assembly rule. This is the floor, never a permission: the authority having jurisdiction can require more and frequently does.

  • Lawn irrigation, no pump, no chemical injection: high hazard, backsiphonage only, so at least PVB. Irrigation is a health hazard because of what is in the soil, not because of the water going in. That surprises people.
  • Lawn irrigation with a fertiliser injector: high hazard, backpressure possible, so at least RP. The injector is a pressure source. The moment chemicals are pumped in, a vacuum breaker is no longer enough.
  • Boiler feed with treatment chemicals: high hazard, backpressure possible, so at least RP. A boiler makes its own pressure and the treatment is toxic. This is the textbook RP.
  • Fire sprinkler, wet pipe, no antifreeze, no booster: low hazard, backpressure possible, so at least DC. Stagnant water in black steel is objectionable rather than dangerous. Add antifreeze or a booster pump and it changes.
  • Fire sprinkler with antifreeze or foam: high hazard, backpressure possible, so at least RP. The additive is the hazard. The same building, the same pipe, a different answer.
  • Carbonated beverage dispenser: high hazard, backpressure possible, so at least RP. Carbon dioxide pressure pushes back, and carbonic acid leaches copper out of the tube. Copper piping is prohibited downstream.
  • Commercial dishwasher or laundry: high hazard, backpressure possible, so at least RP. Detergents and pumped rinse water.
  • Cooling tower with treatment: high hazard, backpressure possible, so at least RP. Treated recirculating water under pump pressure.
  • Hose bibb on a residence: high hazard, backsiphonage only, so at least PVB. A hose left in a bucket or a drain is the classic backsiphonage path. A hose connection vacuum breaker handles it, and it is a device rather than a testable assembly.
  • Food-grade process water, no chemicals, gravity fed: low hazard, backsiphonage only, so at least DC. Objectionable if it came back, not dangerous.
  • Reclaimed or recycled water service: high hazard, backpressure possible, so at least RP. Purple pipe. Treated as a health hazard everywhere.
  • Medical or dental equipment: high hazard, backpressure possible, so at least RP. Aspirators and process equipment can both contaminate and push.
  • Elevated storage tank filled through the top, no pump: low hazard, backpressure possible, so at least DC. The stored column itself is the pressure source. Elevation counts as backpressure even with no pump on site.